B.15 defaults by drive model – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 479

No.
Name
Unit
Default Settings
–
Model CIMR-Po
–
5A0017
5A0022
5A0027
5A0032
o2-04
Drive Model Selection
Hex.
CA
CC
CD
CE
E2-11
Motor Rated Power
kW (HP)
11
(15)
15
(20)
18.5
(25)
22
(30)
b3-04
V/f Gain during Speed Search
%
100
100
100
100
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
0.5
0.5
0.5
0.5
b8-04
Energy Saving Coefficient Value
–
172
154
140
129
C5-17
Motor Inertia
kgm
2
0.053
0.076
0.138
0.165
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
17
22
27
32
E2-02
Motor Rated Slip
Hz
1.7
1.6
1.67
1.7
E2-03
Motor No-Load Current
A
5.1
6.6
8.1
9.6
E2-05
Motor Line-to-Line Resistance
Ω
1.17
0.9
0.66
0.52
E2-06
Motor Leakage Inductance
%
19.6
17.2
20.1
23.5
E2-10
Motor Iron Loss for Torque Compensation
W
385
440
508
586
L2-02
Momentary Power Loss Ride-Thru Time
s
1
2
2
2
L2-03
Momentary Power Loss Minimum Baseblock Time
s
1
1.2
1.2
1.2
L2-04
Momentary Power Loss Voltage Recovery Time
s
0.9
1
1
1
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.27
0.24
0.32
0.36
L8-02
Overheat Alarm Level
°C
120
120
115
115
L8-35
Installation Method Selection
–
2
2
2
2
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
B.15 Defaults by Drive Model
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
479
B
Parameter List