Cause

Possible Solution

In drive models 2A0004 to 2A0056 or 4A0002

to 4A0031, L2-02 was changed from its

default value without installing a Momentary

Power Loss Ride-Thru unit

Correct the setting to L2-02 or install an optional Momentary Power Loss Ride-Thru unit.

Control power supply wiring is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace the control board, the entire drive, or the control power supply. For

instructions on replacing the control board, contact Yaskawa or a Yaskawa representative.

Internal circuitry is damaged

• Cycle power to the drive. Check if the fault reoccurs.
• If the problem continues, replace either the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display

Fault Name

Uv3

Undervoltage 3 (Soft-Charge Bypass Relay Fault)
The soft-charge bypass relay failed.

Cause

Possible Solution

The relay or contactor on the soft-charge

bypass relay is damaged

• Cycle power to the drive and see if the fault reoccurs.
• Check monitor U4-06 for the performance life of the soft-charge bypass relay.
• Replace either the control board or the entire drive if U4-06 exceeds 90%. For instructions on replacing

the control board, contact Yaskawa or a Yaskawa representative.

Digital Operator Display

Fault Name

<1>

Uv4

Gate Drive Board Undervoltage
Voltage drop in the gate drive board circuit

Cause

Possible Solution

Not enough power is being supplied to the gate

drive board.

Cycle power to the drive and see if the fault reoccurs.

Refer to Diagnosing and Resetting Faults on

page 326

for details.

• If the problem continues, replace either the gate drive board or the entire drive. For instructions on

replacing the gate drive board, contact Yaskawa or a Yaskawa representative.

<1> Detected in models 4A0930 and 4A1200.

Digital Operator Display

Fault Name

voF

Output Voltage Detection Fault
Problem detected with the voltage on the output side of the drive.

Cause

Possible Solution

Hardware is damaged. Internal drive module

MC / FAN overheat protection circuit board is

due to abnormal ambient operating power.

• Lower ambient temperature.
• Replace the control board or the entire drive. For instructions on replacing the control board, contact

Yaskawa or a Yaskawa representative.

Digital Operator Display

Fault Name

vToL

VT Overload

Cause

Possible Solution

The output current of the drive has been

elevated for a set length of time.

The application may not be suited for the drive
• The application may not be suited for the drive
• The drive is undersized for the load

6.4 Fault Detection

310

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual