beautypg.com

Figure 5.63, Illustrates how gain and bias settings work, 7 h: terminal functions – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 230

background image

Terminal FM

1.

View the value set to H4-02 (Terminal FM Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in H4-01 will be output from terminal FM.

2.

Adjust H4-02 viewing the monitor connected to the terminal FM.

3.

View the value set to H4-03 on the digital operator; terminal FM will output a voltage equal to 0% of the parameter

being set in H4-01.

4.

Adjust H4-03 viewing the output signal on the terminal FM.

Terminal AM

1.

View the value set to H4-05 (Terminal AM Monitor Gain) on the digital operator. A voltage equal to 100% of the

parameter being set in H4-04 will be output from terminal AM.

2.

Adjust H4-05 viewing the monitor connected to the terminal AM.

3.

View the value set to H4-06 on the digital operator; terminal AM will output a voltage equal to 0% of the parameter

being set in H4-04.

4.

Adjust H4-06 viewing the output signal on the terminal AM.

Output Voltage

Output Voltage

0 V

5 V

10 V

Gain 150%
Bias 0%

Gain = 150%
Bias = 0%

Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%

Gain 100%
Bias 0%

Gain 50%
Bias 0%

100%

Monitor Value

Monitor Value

0%

H4-07, 08 = 0

H4-07, 08 = 1

10 V

-10 V

100%

5 V

15 V

-5 V

-15 V

-100%

Figure 5.63 Analog Output Gain and Bias Setting Example 1 and 2

Set H4-03 to 30% for an output signal of 3 V at terminal FM when the monitored value is at 0%.

Gain = 100%
Bias = 30%

Gain = 100%
Bias = 0%

Gain 100%

Bias 30%

Gain 100%

Bias 0%

Monitor Value

Monitor Value

0 V

3 V

10 V

100%

0%

Output Voltage

Output Voltage

H4-07, 08 = 0

H4-07, 08 = 1

10V

-10 V

100%

3 V

-4 V

-100%

Figure 5.64 Analog Output Gain and Bias Setting Example 3

n

H4-07, H4-08: Multi-Function Analog Output Terminal FM, AM Signal Level Selection

Sets the voltage output level of U parameter (monitor parameter) data to terminal FM and terminal AM using parameters

H4-07 and H4-08.

No.

Name

Setting Range

Default

H4-07

Multi-Function Analog Output Terminal FM

Signal Level Selection

0 to 2

0

H4-08

Multi-Function Analog Output Terminal AM

Signal Level Selection

0 to 2

0

5.7 H: Terminal Functions

230

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: