beautypg.com

F6 and f7: communication option card, F6-01: communications error operation selection, 6 f: option settings – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 198

background image

u

F6 and F7: Communication Option Card

These parameters configure communication option cards and communication fault detection methods.
Some parameters apply to all communication option cards and some parameters apply to certain network options only. The

option cards are applicable to the parameter rows marked with an “O”.

Comm.

Protocol

Parameter Range

F6-01 to

F6-03

F6-04

F6-06 to

F6-08

F6-10 to

F6-14

F6-20,

F6-21

F6-22

F6-23 to

F6-26

F6-30 to

F6-32

F6-35,

F6-36

F6-45 to

F6-49

F6-50 to

F6-63

F7-01 to

F7-15

F7-16

F7-17 to

F7-42

CC-Link

O

O

O

O

MECHA-
TROLINK-II

O

O

O

O

O

MECHA-
TROLINK-
III

O

O

O

O

PROFIBUS-
DP

O

O

O

CANopen

O

O

O

EtherCAT

O

O

BACnet

O

O

DeviceNet

O

O

O

LonWorks

O

O

Modbus
TCP/IP

O

O

O

O

PROFINET

O

O

O

O

EtherNet/IP

O

O

O

O

n

F6-01: Communications Error Operation Selection

Determines drive operation when a communication error occurs.

No.

Parameter Name

Setting Range

Default

F6-01

Communications Error Operation Selection

0 to 3

1

Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)

Setting 1: Coast to Stop

Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)

Setting 3: Alarm Only (Continue Operation)

n

F6-02: External Fault from Comm. Option Detection Selection

Determines the detection method of an external fault initiated by a communication option (EF0).

No.

Parameter Name

Setting Range

Default

F6-02

External Fault from Comm. Option Detection Selection

0, 1

0

Setting 0: Always Detected

Setting 1: Detection during Run Only

n

F6-03: External Fault from Comm. Option Operation Selection

Determines drive operation when an external fault is initiated by a communication option (EF0).

No.

Parameter Name

Setting Range

Default

F6-03

External Fault from Comm. Option Operation Selection

0 to 3

1

Setting 0: Ramp to Stop

5.6 F: Option Settings

198

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: