F6 and f7: communication option card, F6-01: communications error operation selection, 6 f: option settings – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 198

u
F6 and F7: Communication Option Card
These parameters configure communication option cards and communication fault detection methods.
Some parameters apply to all communication option cards and some parameters apply to certain network options only. The
option cards are applicable to the parameter rows marked with an “O”.
Comm.
Protocol
Parameter Range
F6-01 to
F6-03
F6-04
F6-06 to
F6-08
F6-10 to
F6-14
F6-20,
F6-21
F6-22
F6-23 to
F6-26
F6-30 to
F6-32
F6-35,
F6-36
F6-45 to
F6-49
F6-50 to
F6-63
F7-01 to
F7-15
F7-16
F7-17 to
F7-42
CC-Link
O
O
O
O
–
–
–
–
–
–
–
–
–
–
MECHA-
TROLINK-II
O
–
O
–
O
O
O
–
–
–
–
–
–
–
MECHA-
TROLINK-
III
O
–
O
–
O
–
O
–
–
–
–
–
–
–
PROFIBUS-
DP
O
–
O
–
–
–
–
O
–
–
–
–
–
–
CANopen
O
–
O
–
–
–
–
–
O
–
–
–
–
–
EtherCAT
O
–
O
–
–
–
–
–
–
–
–
–
–
–
BACnet
O
–
–
–
–
–
–
–
–
O
–
–
–
–
DeviceNet
O
–
O
–
–
–
–
–
–
–
O
–
–
–
LonWorks
O
–
O
–
–
–
–
–
–
–
–
–
–
–
Modbus
TCP/IP
O
–
O
–
–
–
–
–
–
–
–
O
O
–
PROFINET
O
–
O
–
–
–
–
–
–
–
–
O
–
O
EtherNet/IP
O
–
O
–
–
–
–
–
–
–
–
O
–
O
n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error Operation Selection
0 to 3
1
Setting 0: Ramp to Stop (Use the Deceleration Time Set to C1-02)
Setting 1: Coast to Stop
Setting 2: Fast Stop (Use the Fast Stop Time Set to C1-09)
Setting 3: Alarm Only (Continue Operation)
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Detection Selection
0, 1
0
Setting 0: Always Detected
Setting 1: Detection during Run Only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines drive operation when an external fault is initiated by a communication option (EF0).
No.
Parameter Name
Setting Range
Default
F6-03
External Fault from Comm. Option Operation Selection
0 to 3
1
Setting 0: Ramp to Stop
5.6 F: Option Settings
198
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual