beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 249

background image

Setting 5: Overexcitation Deceleration 2

Overexcitation Deceleration 2 slows down the motor while trying to maintain the DC bus voltage at the level set to parameter

L3-17. This function shortens the achievable deceleration time more than by using Overexcitation Deceleration 1. Setting 5

will shorten/lengthen the decel time to maintain the L3-17 bus level.

Refer to Overexcitation Deceleration (Induction

Motors) on page 264

for details.

n

L3-05: Stall Prevention Selection during Run

Determines how Stall Prevention works during Run. Stall Prevention during run prevents the motor from stalling by

automatically reducing the speed when a transient overload occurs while the motor is running at constant speed.

No.

Name

Setting Range

Default

L3-05

Stall Prevention Selection During Run

0 to 2

1

Note:

Stall Prevention during run is disabled when the output frequency is 6 Hz or lower regardless of the L3-05 and L3-06 settings.

Setting 0: Disabled

Drive runs at the set frequency reference. A heavy load may cause the motor to stall and trip the drive with an oC or oL fault.

Setting 1: Decelerate using C1-02

If the current exceeds the Stall Prevention level set in parameter L3-06, the drive will decelerate at decel time 1 (C1-02). When

the current level drops below the value of L3-06 minus 2% for 100 ms, the drive accelerates back to the frequency reference

at the active acceleration time.

Setting 2: Decelerate using C1-04

Same as setting 1 except the drive decelerates at decel time 2 (C1-04).

n

L3-06: Stall Prevention Level during Run

Sets the current level to trigger Stall Prevention during run. Depending on the setting of parameter L3-23, the level is

automatically reduced in the constant power range (speed beyond base speed). A setting of 100% is equal to the drive rated

current.
The Stall Prevention level can be adjusted using an analog input.

Refer to Multi-Function Analog Input Terminal Settings

on page 227

for details.

No.

Name

Setting Range

Default

L3-06

Stall Prevention Level During Run

30 to 150%

<1>

<1>

<1> The upper limit and default for this setting is determined by L8-38.

n

Overvoltage Suppression Function

Suppresses overvoltage faults by decreasing the regenerative torque limit and slightly increasing the output frequency when

the DC bus voltage rises. This function can drive loads with cyclic regenerative operation, such as a punch press or other

applications that involve repetitive crank movements.
The regenerative torque limit and the output frequency are adjusted during ov suppression so that the DC bus voltage does

not exceed the level set to parameter L3-17. In addition to the parameters explained below, ov suppression also uses these

settings for frequency adjustment:
• DC bus voltage gain (L3-20)
• Deceleration rate calculations gain (L3-21)
• Inertia calculations for motor acceleration time (L3-24)
• Load inertia ratio (L3-25)

Note:

1. The motor speed will exceed the frequency reference when overvoltage suppression is triggered. Consequently, overvoltage suppression

is not appropriate in applications that require a perfect match between the frequency reference and the motor speed.

2. Disable overvoltage suppression when using a braking resistor.
3. Overvoltage may still occur if there is a sudden increase to a regenerative load.
4. This function is enabled only when operating just below the maximum frequency. Overvoltage suppression does not increase the output

frequency beyond the maximum frequency. If the application requires this, increase the maximum frequency and change the base

frequency setting.

n

L3-11: Overvoltage Suppression Function Selection

Enables or disables the overvoltage suppression function.

5.8 L: Protection Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

249

5

Parameter Details

This manual is related to the following products: