Setting 0: No Initialize
Setting 1110: User Initialize

Resets parameters to the values selected by the user as User Settings. User Settings are stored when parameter o2-03 is set to

“1: Set defaults”.

Note:

User Initialization resets all parameters to a user-defined set of default values previously saved to the drive. Set parameter o2-03 to 2 to

clear the user-defined default values.

Setting 2220: 2-Wire Initialization

Resets parameters to default settings with digital inputs S1 and S2 configured as Forward run and Reverse run, respectively.

Refer to Setting 40, 41: Forward Run, Reverse Run Command for 2-Wire Sequence on page 211

for more information on

digital input functions.

Setting 3330: 3-Wire Initialization

Resets parameters to default settings with digital inputs S1, S2, and S5 configured as Run, Stop, and Forward/Reverse

respectively.

Refer to Setting 0: 3-Wire Sequence on page 205

for more information on digital input functions.

Notes on Parameter Initialization

The parameters shown in

Table 5.1

will not be reset when the drive is initialized by setting A1-03 = 2220 or 3330.

Table 5.1 Parameters Not Changed by Drive Initialization

No.

Parameter Name

A1-00

Language Selection

E1-03

V/f Pattern Selection

F6-08

Communication Parameter Reset

L8-35

Installation Selection

o2-04

Drive/kVA Selection

Setting 5550: Terminal/Control Initialize

An oPE04 error appears on the digital operator when a terminal block with settings saved to its built-in memory is installed

in a drive that has edited parameters. Set A1-03 to 5550 to use the parameter settings saved to the terminal block memory.

Setting 8008: Pump

Application Preset for pump applications.

Refer to Application Selection on page 126

for a list of parameters and default

values for this Application Preset.

Setting 8009: Pump w/ PI

Application Preset for pump applications.

Refer to Application Selection on page 126

for a list of parameters and default

values for this Application Preset.

Setting 8010: Fan

Application Preset for pump applications.

Refer to Application Selection on page 126

for a list of parameters and default

values for this Application Preset.

Setting 8011: Fan w/ PI

Application Preset for pump applications.

Refer to Application Selection on page 126

for a list of parameters and default

values for this Application Preset.

n

A1-04, A1-05: Password and Password Setting

Parameter A1-04 enters the password when the drive is locked; parameter A1-05 is a hidden parameter that sets the password.

No.

Parameter Name

Setting Range

Default

A1-04

Password

0000 to 9999

0000

A1-05

Password Setting

How to Use the Password

The user can set a password in parameter A1-05 to restrict access to the drive. The password must be entered to A1-04 to

unlock parameter access (i.e., parameter setting A1-04 must match the value programmed into A1-05). The following

parameters cannot be viewed or edited until the value entered to A1-04 correctly matches the value set to A1-05: A1-01,A1-03,

A1-06, and A2-01 through A2-33.
The instructions below demonstrate how to set password “1234”. An explanation follows on how to enter that password to