Figure 5.84 Output Frequency Reduction During Overheat Alarm

n

L8-19: Frequency Reduction Rate during Overheat Pre-Alarm

Specifies the output frequency reduction when L8-03 is set to 4 and an oH alarm is present. Set as a factor of the maximum

output frequency.

No.

Name

Setting Range

Default

L8-19

Frequency Reduction Rate During Overheat Pre-Alarm

0.1 to 0.9

0.8

n

L8-05: Input Phase Loss Protection Selection

Enables or disables the input phase loss detection.

No.

Name

Setting Range

Default

L8-05

Input Phase Loss Protection Selection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

Enables input phase loss detection. Since measuring the DC bus ripple detects input phase loss, a power supply voltage

imbalance or main circuit capacitor deterioration may also trigger a phase loss fault (PF).
Detection is disabled if:
• The drive is decelerating.
• No Run command is active.
• Output current is less than or equal to 30% of the drive rated current.

n

L8-07: Output Phase Loss Protection Selection

Enables or disables the output phase loss detection triggered when the output current falls below 5% of the drive rated current.

Note:

Output phase loss detection can mistakenly be triggered if the motor rated current is very small compared to the drive rating. Disable this

parameter in such cases.

No.

Name

Setting Range

Default

L8-07

Output Phase Loss Protection Selection

0 to 2

1

Setting 0: Disabled
Setting 1: Fault when One Phase Is Lost

An output phase loss fault (LF) is triggered when one output phase is lost. The output shuts off and the motor coasts to stop.

5.8 L: Protection Functions

258

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual