Considering derating, For details – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 260

background image

n

L8-18: Software Current Limit Selection

Enables and disables the Software Current Limit (CLA) protection function to prevent main circuit transistor failures caused

by high current.

Note:

Do not change this setting unless absolutely necessary.

No.

Name

Setting Range

Default

L8-18

Software Current Limit Selection

0, 1

0

Setting 0: Software CLA Disabled

The drive may trip on an oC fault if the load is too heavy or the acceleration is too short.

Setting 1: Software CLA Enabled

When the Software CLA current level is reached, the drive reduces the output voltage to reduce the current. Normal operation

continues when the current level drops below the Software CLA level.

n

L8-32: Cooling Fan Failure Selection

Determines drive operation when a FAn fault occurs.

No.

Name

Setting Range

Default

L8-32

Cooling Fan Failure Selection

0 to 4

1

Setting 0: Ramp to Stop

The drive stops the motor using the deceleration time set in parameter C1-02.

Setting 1: Coast to Stop

The drive output is switched off and the motor coasts to a stop.

Setting 2: Fast Stop

The drive stops the motor using the Fast stop time set in parameter C1-09.

Setting 3: Alarm Only

The operation is continued and a FAn alarm is displayed on the digital operator.

Setting 4: Operation with Reduced Speed

The operation is continued, but the speed is reduced to the level set in parameter L8-19.

Note:

“FAn” is detected as an error when Settings 0 or 2 are selected; it is detected as an alarm when Settings 3 or 4 are selected.

n

L8-35: Installation Method Selection

Selects the type of installation for the drive and changes the drive overload (oL2) limits accordingly.

Refer to Temperature

Derating on page 411

for details.

Note:

1. Initialization does not reset this parameter.
2. The value is preset to the appropriate value when the drive is shipped. Change the value only when using Side-by-Side installation or

when mounting a standard drive with the heatsink outside the cabinet.

No.

Name

Setting Range

Default

L8-35

Installation Method Selection

0 to 3

<1>

<1> Default setting is determined by drive model.

Setting 2: Model code 2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242
Setting 0: Model code 2A0250 to 2A0415 and 4A0208 to 4A1200.

Setting 0: IP00/Open-Chassis Enclosure

For an Open Type enclosure drive installed with at a minimum of 30 mm space to the next drive or a cabinet wall.

Setting 1: Side-by-Side Mounting

For drives mounted according to Yaskawa Side-by-Side specifications (requires 2 mm between drives).

Setting 2: IP20/NEMA Type 1 Enclosure

For drives compliant with IP20/NEMA Type 1 enclosure specifications.

Setting 3: Finless Drive or External Heatsink Installation

For finless drives or a standard drive mounted with the heatsink outside the cabinet or enclosure panel.

5.8 L: Protection Functions

260

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual