Table 5.36 LO/RE Key and b1-07

o2-01

b1-07

Switch from LOCAL to REMOTE

Switch from REMOTE to LOCAL

0

0

Not possible

Not possible

1

Not possible

Not possible

1

0

Will not run until a new Run command is

entered.

Run not possible

1

If a Run command is entered, the drive will start

running as soon as the LO/RE key is pushed to

change from LOCAL to REMOTE.

Run not possible

n

o2-02: STOP Key Function Selection

Determines if the STOP key on the digital operator will stop drive operation when the drive is controlled from a remote source

(i.e., not from digital operator).

No.

Name

Setting Range

Default

o2-02

STOP Key Function Selection

0, 1

1

Setting 0: Disabled

Setting 1: Enabled

The STOP key will terminate drive operation even if the Run command source is not assigned to the digital operator. Cycle

the Run command to restart the drive if the drive has been stopped by pressing the STOP key.

n

o2-03: User Parameter Default Value

After completely setting up drive parameters, save the values as user-set defaults with parameter o2-03. After saving the values,

parameter A1-03 (Initialize Parameters) will offer the choice of "1110: User Initialize". Selecting 1110 resets all parameters

to the user-set default values.

Refer to A1-03: Initialize Parameters on page 142

for details on drive initialization.

No.

Name

Setting Range

Default

o2-03

User Parameter Default Value

0 to 2

0

Setting 0: No Change (Awaiting Command)

Setting 1: Set User Initialize Values

The current parameter settings are saved as user-set default for a later User Initialization. Setting o2-03 to 1 and pressing the

ENTER key saves the values and returns the display to 0.

Setting 2: Clear User Initialize Values

All user-set defaults for “User Initialize” are cleared. Setting o2-03 to 2 and pressing the ENTER key erases the values and

returns the display to 0.

n

o2-04: Drive Model Selection

Set this parameter when replacing the control board or the terminal board.

Refer to Defaults by Drive Model on page 466

for

information on drive model selection.

NOTICE:

Drive performance will suffer and protective functions will not operate properly if the correct drive capacity is not set to o2-04.

No.

Name

Setting Range

Default

o2-04

Drive Model Selection

-

Determined by

drive capacity

Note:

Change o2-04 setting only when necessary.

n

o2-05: Frequency Reference Setting Method Selection

Determines if the ENTER key must be pressed after changing the frequency reference using the digital operator while in the

Drive Mode.

No.

Name

Setting Range

Default

o2-05

Frequency Reference Setting Method Selection

0, 1

0

5.10 o: Operator Related Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

269

5

Parameter Details