100

85

70

55

0

L8-35 = 2: IP20/NEMA Type 1 Enclosure
L8-35 = 3: External Heatsink lnstallation

L8-35 = 0: IP00/Open-Chassis Enclosure

30

-10

40

50

Drive Rating

(%)

L8-12
(Ambient temp:

°C)

L8-35 = 1: Side-by-Side Mounting

Figure A.1 Ambient Temperature and Installation Method Derating

u

Altitude Derating

The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive

rated voltage and the rated output current must be derated for 0.2% per 100 m.