2. When setting more than one Jump frequency, make sure that the parameters do not overlap.

u

d4: Frequency Reference Hold and Up/Down 2 Function

n

d4-01: Frequency Reference Hold Function Selection

Determines whether the frequency reference or the frequency bias (Up/Down 2) value is saved when the Stop command is

entered or the power supply is shut down. This parameter is effective when either of the digital input functions listed below

are used:
• Accel/decel ramp hold function (H1-oo= A)
• Up/Down function (H1-oo = 10 and 11)
• Up/Down 2 function (H1-oo = 75 and 76)

No.

Parameter Name

Setting Range

Default

d4-01

Frequency Reference Hold Function Selection

0, 1

0

The operation depends on the function used with parameter d4-01.

Setting 0: Disabled

• Acceleration hold

The hold value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off. The active

frequency reference will be the value the drive uses when it restarts.

• Up/Down

The frequency reference value will be reset to 0 Hz when the Stop command is entered or the drive power is switched off.

The drive will start from 0 Hz when it is restarted.

• Up/Down 2

The frequency bias is not saved when the Stop command is entered, or 5 s after the Up/Down 2 command has been released.

The Up/Down 2 function will start with a bias of 0% when the drive is restarted.

Setting 1: Enabled

• Acceleration hold

The last hold value will be saved when the Run command or the drive power is switched off and the drive will use the saved

value as the frequency reference when it restarts. Make sure to continuously enable the multi-function input terminal set for

“Accel/decel ramp hold” (H1-oo = A) or the hold value will be cleared when the power is switched on.

Power supply

Forward Run / Stop

Hold Accel/Decel

Frequency reference

Output frequency

d4-01 = 1

d4-01 = 0

Hold

Hold

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

ON

Figure 5.30 Frequency Reference Hold with Accel/Decel Hold Function

• Up/Down

The frequency reference value will be saved when the Run command or the drive power is switched off. The drive will use

the frequency reference that was saved when it restarts.

• Up/Down 2 with frequency reference from digital operator

When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the Up/Down 2 bias value is

added to the frequency reference and then reset to 0. This new frequency reference is saved and will also be used to restart

the drive after the power is cycled.

5.4 d: Reference Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

185

5

Parameter Details