Setting

Function

Page

AF

Emergency Override Forward Run

214

Setting

Function

Page

B0

Emergency Override Reverse Run

214

Setting 0: 3-Wire Sequence

The digital input programmed for 3-Wire control becomes the forward/reverse directional input, S1 becomes the Run command

input, and S2 becomes the Stop command input.
The drive starts the motor when the input S1 set for the Run command closes for longer than 2 ms. The drive stops the operation

when the Stop input S2 is released. When the digital input programmed for a forward/reverse operation is open, the drive is

set for forward operation. When the digital input is closed, the drive is set for reverse operation.

Note:

Input the Run and Stop commands via S1 and S2 when selecting a 3-Wire sequence.

S1

S2

S5

SN

Run Command (Runs when Closed)

DRIVE

Stop Switch

(N.C.)

Run Switch

(N.O.)

Stop Command (Stops when Open)

FWD/REV (Multi-Function Input)

(H1-05 = 0)
Standard Digital Input Common

Figure 5.36 3-Wire Sequence Wiring Diagram

Figure 5.61

2 ms min.

Run command

Can be
ON or OFF

2 ms min.

ON (reverse)

d

r

a

w

o

F

p

o

t

S

e

s

r

e

v

e

R

p

o

t

S

Can be either ON or OFF

OFF (forward)

Forward

Motor speed

Forward/reverse
command

Stop command

Figure 5.37 3-Wire Sequence

Note:

1. The Run command must be closed for more than 2 ms.
2. If the Run command is active at power up and b1-17 = 0 (Run command at power up not accepted), the Run LED will flash to indicate

that protective functions are operating. If required by the application, set b1-17 to 1 to automatically issue the Run command upon drive

power up.

WARNING!

Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the correct state before applying

power to the drive. Failure to comply could result in death or serious injury from moving equipment.
WARNING!

Sudden Movement Hazard. The drive may start unexpectedly in reverse direction after power up if it is wired for 3-Wire sequence

but set up for 2-Wire sequence (default). Make sure b1-17 is set to “0” (drive does not accept a Run command active at power up). When

initializing the drive use 3-Wire initialization. Failure to comply could result in death or serious injury from moving equipment.

Setting 1: LOCAL/REMOTE Selection

This setting allows the input terminal to determine if the drive will run in LOCAL mode or REMOTE mode.

Status

Description

Closed

LOCAL: Frequency reference and Run command are input from the digital operator.

Open

REMOTE: Frequency reference and Run command are input from the selected external reference. If a digital input set to H1-oo = 2

is active, they will be read from external reference source 2 (b1-15 and b1-16). In all other cases they will be read from external reference

source 1 (b1-01 and b1-02).

Note:

1. The LO/RE key on the digital operator is disabled when one of the multi-function input terminals is set to for LOCAL/REMOTE.
2. When the drive is set to LOCAL, the LO/RE LED will light.
3. The default setting of the drive does not allow switching between LOCAL and REMOTE during run. To allow the drive to switch

between LOCAL and REMOTE during run,

Refer to b1-07: LOCAL/REMOTE Run Selection on page 151

.

5.7 H: Terminal Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

205

5

Parameter Details