L2-11 (Desired DC Bus Voltage)

0 Hz

DC bus voltage

0 V

0 V

KEB Digital Input

Main Power Supply

Output Frequency

L2-10

KEB deceleration is
triggered by DC bus voltage

KEB restart triggered by
digital input release

L2-02

(Power Loss

Ride-Thru Time)

L2-05 (Uv Detection Level)

0 Hz

0 V

0 V

L2-10

KEB deceleration is
triggered by DC bus voltage

KEB restart after
L2-02 has passed

L2-02

(Power Loss

Ride-Thru Time)

Power Loss

Power Loss

Power loss longer than L2-02

Power loss shorter than L2-02

L2-05 (Uv Detection Level)

L2-11 (Desired DC Bus Voltage)

Figure 5.73 KEB Operation Using L2-02 and KEB Input

KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Not Used

Here, L2-01 = 4 and the input terminals have not been set for KEB Ride-Thru (H1-oo does not equal 65, 66, 7A, 7B). After

decelerating for the time set to parameter L2-10, the drive checks the DC bus voltage level. Deceleration continues if the DC

bus voltage is lower than the level set in L2-11. Normal operation resumes when the DC bus voltage rises above the value of

L2-11.

L2-11 (Desired DC Bus Voltage)

L2-05 (Uv Detection Level)

0 Hz

0 V

0 V

KEB Deceleration

Acceleration using L2-07 or
C1-01/03/05/07 if L2-07 = 0

Power Loss Shorter than L2-10

Power Loss Longer than L2-10

Power Loss

DC Bus Voltage

Main Power Supply

Output Frequency

L2-10

(Min. KEB Operation

Time)

L2-11 (Desired DC Bus Voltage)

L2-05 (Uv Detection Level)

0 Hz

0 V

0 V

KEB Deceleration

Acceleration using L2-07 or
C1-01/03/05/07 if L2-07 = 0

Power Loss

L2-10

(Min. KEB
Op. Time)

Figure 5.74 KEB Operation Using L2-10, Without KEB Input

KEB Ride-Thru Operation as Long as CPU Has Power, KEB Input Used

Here, L2-01 = 3 and an input terminal is set to issue KEB Ride-Thru (H1-oo = 65, 66, 7A, 7B). After decelerating for the

time set to parameter L2-10, the drive checks the DC bus voltage and the status of the digital input. Deceleration continues if

the DC bus voltage is still below the level set in L2-11 or if the digital input assigned to KEB Ride-Thru is still active. Normal

operation resumes when the DC bus voltage rises above the value of L2-11 and the terminal that initiated KEB Rid-Thru is

released.