D4-03: frequency reference bias step (up/down 2) – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 186

Bias
Output
frequency
Bias is added to frequency
reference and reset to 0
Up 2 command
Frequency
reference
5 s
5 s
Figure 5.31 Up/Down 2 Example with Reference from Digital Operator and d4-01 = 1
• Up/Down 2 with frequency reference from input sources other than the digital operator
When a Run command is active and the Up/Down 2 command is released for longer than 5 s, the bias value will be saved
in parameter d4-06. When restarting after the power is switched off, the drive will add the value saved in d4-06 as a bias to
the frequency reference.
Bias
Output
frequency
Up 2 command
d4-06 value
5 s
Bias is saved in parameter d4-06
5 s
Figure 5.32 Up/Down 2 Example with Other Reference than Digital Operator and d4-01 = 1
Note:
Set the limits for Up/Down 2 properly when using d4-01 = 1 in combination with the Up/Down 2 function.
Reference Bias Upper Limit (Up/Down 2) on page 188
Refer to d4-09: Frequency Reference Bias Lower Limit (Up/Down 2) on
for details on the limit settings.
Clearing the Saved Value
Depending on which function is used, it is possible to clear the saved frequency reference value by:
• Releasing the input programmed for Acceleration hold.
• Setting an Up or Down command while no Run command is active.
• Resetting parameter d4-06 to zero.
Refer to d4-06: Frequency Reference Bias (Up/Down 2) on page 188
n
d4-03: Frequency Reference Bias Step (Up/Down 2)
Sets the bias added to or subtracted from the frequency reference by the Up/Down 2 function.
No.
Parameter Name
Setting Range
Default
d4-03
Frequency Reference Bias Step (Up/Down 2)
0.00 to 99.99 Hz
0.00 Hz
The operation depends on the set value:
Setting d4-03 = 0.00 Hz
While the Up 2 or Down 2 command is enabled, the bias value is increased or decreased using the accel/decel times determined
by parameter d4-04.
5.4 d: Reference Settings
186
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual