Monitor data – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 499

background image

Register No.

Contents

000FH

Control Selection Setting
bit 0

Reserved

bit 1

PID Setpoint Input

bit 2, 3

Reserved

bit 4

PI2 Target Input

bit 5 to B

Reserved

bit C

Enable Terminal S5 Input for Broadcast Data

bit D

Enable Terminal S6 Input for Broadcast Data

bit E

Enable Terminal S7 Input for Broadcast Data

bit F

Enable Terminal S8 Input for Broadcast Data

0010H to 001AH

Reserved

001BH

Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)

001CH

Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)

001DH to 001FH

Reserved

3004H

Set Time – Hours/Minutes (HHmm)

3005H

Set Date – Year/Day of Week (YYdd)

3006H

Set Date – Month/Day (MMDD)

3007H

RTC Set Command/Statud

0 = Complete

1 = Set RTC data using registers 3004H to 3006H

8 = failed

302FH

RTC Enter

0 = Overwrite RTC data using registers 3004H to 3006H. Only effective when 3030H bit 1 (RTC Enter Enable) is set.

3030H

bit 1

RTC Enter Enable

bit 2

RTC TIE Fault Enable

u

Monitor Data

Monitor data can be read only.

Register No.

Contents

0020H

Drive Status 1
bit 0

During Run

bit 1

During Reverse

bit 2

Drive Ready

bit 3

Fault

bit 4

Data Setting Error

bit 5

Multi-Function Contact Output (terminal M1-M2)

bit 6

bit 7

bit 8 to bit D

Reserved

bit E

ComRef status

bit F

ComCtrl status

C.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

499

C

MEMOBUS/Modbus Communications

This manual is related to the following products: