beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 158

background image

No.

Parameter Name

Setting Range

Default

b3-14

Bi-Directional Speed Search Selection

0, 1

1

Setting 0: Disabled

The drive uses the frequency reference to determine the direction of motor rotation to restart the motor.

Setting 1: Enabled

The drive detects the motor rotation direction to restart the motor.

n

b3-17: Speed Search Restart Current Level

Sets the current level at which Speed Estimation is restarted as a percentage of drive rated current to avoid overcurrent and

overvoltage problems since a large current can flow into the drive if the difference between the estimated frequency and the

actual motor speed is too big when performing Speed Estimation.

No.

Name

Setting Range

Default

b3-17

Speed Search Restart Current Level

0 to 200%

150%

n

b3-18: Speed Search Restart Detection Time

Sets the time for which the current must be above the level set in b3-17 before restarting Speed Search.

No.

Name

Setting Range

Default

b3-18

Speed Search Restart Detection Time

0.00 to 1.00 s

0.10 s

n

b3-19: Number of Speed Search Restarts

Sets the number of times the drive should attempt to find the speed and restart the motor. If the number of restart attempts

exceeds the value set to b3-19, the SEr fault will occur and the drive will stop.

No.

Name

Setting Range

Default

b3-19

Number of Speed Search Restarts

0 to 10

3

n

b3-24: Speed Search Method Selection

Sets the Speed Search method.

No.

Parameter Name

Setting Range

Default

b3-24

Speed Search Method Selection

0, 1

0

Setting 0: Current Detection
Setting 1: Speed Estimation

Note:

Refer to Current Detection Speed Search (b3-24 = 0) on page 153

and

Refer to Speed Estimation Type Speed Search (b3-24 = 1) on

page 154

for explanations of the Speed Search methods.

n

b3-25: Speed Search Wait Time

Sets the wait time between Speed Search restarts. Increase the wait time if problems occur with overcurrent, overvoltage, or

if the SEr fault occurs.

No.

Name

Setting Range

Default

b3-25

Speed Search Wait Time

0.0 to 30.0 s

0.5 s

n

b3-26: Direction Determining Level

Sets the level that determines the direction of motor rotation. Increase this value if the drive fails to detect the direction of the

motor correctly.

Note:

This parameter is only available in models 4A0930 and 4A1200.

No.

Name

Setting Range

Default

b3-26

Direction Determining Level

40 to 60000

Determined by

o2-04

5.2 b: Application

158

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: