L5: fault restart – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 253

background image

n

L4-06: Frequency Reference at Reference Loss

Sets the frequency reference level at which the drive runs when L4-05 = 1 and when detecting a reference loss. The value is

set as a percentage of the frequency reference before the loss was detected.

No.

Name

Setting Range

Default

L4-06

Frequency Reference at Reference Loss

0.0 to 100.0%

80.0%

n

L4-07: Speed Agree Detection Selection

Determines when frequency detection is active using parameters L4-01 through L4-04.

No.

Name

Setting Range

Default

L4-07

Speed Agree Detection Selection

0, 1

0

Setting 0: No Detection during baseblock
Setting 1: Detection always enabled

u

L5: Fault Restart

After a fault has occurred, Fault Restart attempts to automatically restart the motor and continue operation instead of stopping.
The drive can perform a self-diagnostic check and resume the operation after a fault has occurred. If the self-check is successful

and the cause of the fault has disappeared, the drive restarts by first performing Speed Search (

Refer to b3: Speed Search on

page 153

for details).

Note:

1. The wiring sequence should remove the Forward/Reverse command when a fault is triggered and output is shut off.
2. When the Forward/Reverse command is removed, the drive can perform a self-diagnostic check and attempt to restart the fault

automatically.

WARNING!

Sudden Movement Hazard. Do not use the fault restart function in lifting applications. Fault restart may cause the machine to

drop the load, which could result in death or serious injury.

The drive can attempt to restart itself following the faults listed below.

Fault

Name

Fault

Name

GF

Ground Fault

oL4

Overtorque 2

LF

Output Open Phase

ov

DC Bus Overvoltage

oC

Overcurrent

PF

Input Phase Loss

oH1

Drive Overheat

rH

Braking Resistor Fault

oL1

Motor Overload

rr

Braking Transistor Fault

oL2

Drive Overload

Uv1

DC Bus Undervoltage

<1>

oL3

Overtorque 1

<1> When L2-01 is set to 1 through 4 (continue operation during momentary power loss)

Use parameters L5-01 to L5-05 to set up automatic fault restart.
Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart.

n

L5-01: Number of Auto Restart Attempts

Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,

the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter

reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.

No.

Name

Setting Range

Default

L5-01

Number of Auto Restart Attempts

0 to 10 Times

0 Times

5.8 L: Protection Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

253

5

Parameter Details