L8: drive protection – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 256

background image

Setting 5: UL3, UL4 at speed agree (Alarm)

Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during

acceleration and deceleration. The operation continues after detecting overtorque and triggering a UL3/UL4 alarm.

Setting 6: UL3, UL4 at Run (Alarm)

Undertorque detection works as long as the Run command is active. The operation continues after detecting overtorque and

triggering a UL3/UL4 alarm.

Setting 7: UL3, UL4 at Speed Agree (Fault)

Undertorque detection is active only when the output speed is equal to the frequency reference, i.e., no detection during

acceleration and deceleration. The operation stops and triggers a UL3/UL4 fault.

Setting 8: UL3, UL4 at run (Fault)

Undertorque detection works as long as a Run command is active. The operation stops and triggers a UL3/UL4 fault.

Setting 9: UL6 at speed agree (Alarm)
Setting 10: UL6 during run (Alarm)
Setting 11: UL6 at speed agree (Fault)
Setting 12: UL6 during run (Fault)

n

L6-02, L6-05: Torque Detection Level 1, 2

These parameters set the detection levels for torque detection functions 1 and 2 as a percentage of the drive rated output current.

No.

Name

Setting Range

Default

L6-02

Torque Detection Level 1

0 to 300%

150%

L6-05

Torque Detection Level 2

0 to 300%

150%

Note:

The torque detection level 1 (L6-02) can also be supplied by an analog input terminal set to H3-oo = 7. Here, the analog value has priority

and the setting in L6-02 is disregarded. Torque detection level 2 (L6-05) cannot be set by an analog input.

n

L6-03, L6-06: Torque Detection Time 1, 2

These parameters determine the time required to trigger an alarm or fault after exceeding the levels in L6-02 and L6-05.

No.

Name

Setting Range

Default

L6-03

Torque Detection Time 1

0.0 to 10.0 s

0.1 s

L6-06

Torque Detection Time 2

0.0 to 10.0 s

0.1 s

n

L6-13: Motor Underload Protection Selection

Sets the motor underload protection (UL6) based on motor load.

No.

Name

Setting Range

Default

L6-13

Motor Underload Protection Selection

0, 1

0

Setting 0: Base frequency enable
Setting 1: Max frequency enable

n

L6-14: Motor Underload Protection Level at Minimum Frequency

Sets the motor underload protection (UL6) based on motor load.

No.

Name

Setting Range

Default

L6-14

Motor Underload Protection Level at Minimum Frequency

0 to 300%

15%

u

L8: Drive Protection

n

L8-01: Internal Dynamic Braking Resistor Protection Selection (ERF type)

Selects the dynamic braking resistor protection when using an optional heatsink mounted braking resistor (ERF type, 3% ED).

Note:

No.

Name

Setting Range

Default

L8-01

Internal Dynamic Braking Resistor Protection Selection

(ERF type)

0, 1

0

5.8 L: Protection Functions

256

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual