n

L2-04: Momentary Power Loss Voltage Recovery Ramp Time

Sets the time for the drive to restore the output voltage to the level specified by the V/f pattern after Speed Search. The setting

value determines the time for the voltage to go from 0 V to the maximum voltage.

No.

Name

Setting Range

Default

L2-04

Momentary Power Loss Voltage Recovery Ramp Time

0.0 to 5.0 s

Determined by o2-04

n

L2-05: Undervoltage Detection Level (Uv)

Determines the voltage at which a Uv1 fault is triggered or at which the KEB function is activated. This setting rarely needs

to be changed.

No.

Name

Setting Range

Default

L2-05

Undervoltage Detection Level

150 to 210 Vdc

<1>

Determined by

E1-01

<2>

<1> Values are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> The default setting for 400 V class drives depends on whether the drive input voltage is over 400 V or under 400 V.

Note:

1. Install an AC reactor option on the input side of the power supply when setting L2-05 below the default value to prevent damage to

drive circuitry.

2. If using KEB Ride-Thru and L2-05 is set too low, then undervoltage in the DC bus (Uv1) will be triggered before KEB Ride-Thru can

be executed. Take caution not to set this value too low.

n

L2-06: KEB Deceleration Time

Sets the time to decelerate from the frequency reference at the time KEB Ride-Thru was initiated to zero speed. This setting

can be used only when L2-29 = 2 ( System KEB Ride-Thru 1).

No.

Name

Setting Range

Default

L2-06

KEB Deceleration Time

0.00 to 6000.0 s

<1>

0.00 s

<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes

0.00 to 600.00 s.

n

L2-07: KEB Acceleration Time

Sets the time to reaccelerate from the speed when KEB was deactivated to the frequency reference.
When set to 0.0 s, the drive will accelerate to speed according to the active acceleration time set in C1-01 or C1-03.

No.

Name

Setting Range

Default

L2-07

KEB Acceleration Time

0.00 to 6000.0 s

<1>

0.00 s

<1> Setting range is determined by the accel/decel time units set in C1-10. If the time is set in units of 0.01 s (C1-10 = 0), the setting range becomes

0.00 to 600.00 s.

n

L2-08: Frequency Gain at KEB Start

When the KEB Ride-Thru command is input, the output frequency is reduced in a single step to quickly get the motor into a

regenerative state. Calculate the amount of this frequency reduction using the formula below. L2-08 can only be used with

induction motors.
Amount of reduction = Slip frequency prior to KEB × (L2-08/100) × 2

No.

Name

Setting Range

Default

L2-08

Frequency Gain at KEB Start

0 to 300%

100%

n

L2-10: KEB Detection Time (Minimum KEB Time)

No.

Name

Setting Range

Default

L2-10

KEB Detection Time

0 to 2000 ms

50 ms

n

L2-11: DC Bus Voltage Setpoint during KEB

Determines the setpoint (target value) for the DC bus voltage during Single KEB Ride-Thru 2. For Single KEB Ride-Thru 1

and System KEB Ride-Thru, parameter L2-11 defines the voltage level to end KEB Ride-Thru.

5.8 L: Protection Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

245

5

Parameter Details