beautypg.com

U3: fault history, For a complete list of u3 – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 461

background image

u

U3: Fault History

No.

(Addr.

Hex)

Name

Description

Analog Output Level

Unit

U3-01 to

U3-04

(90 to 93

(800 to

803))

First to 4th Most Recent

Fault

Displays the first to the fourth most recent faults.

No signal output

available

U3-05 to

U3-10

(804 to

809)

5th to 10th Most Recent

Fault

Displays the fifth to the tenth most recent faults.

After ten faults, data for the oldest fault is deleted. The most recent fault

appears in U3-01, with the next most recent fault appearing in U3-02. The

data is moved to the next monitor parameter each time a fault occurs.

No signal output

available

U3-11 to

U3-14

(94 to 97

(80A to

80D))

Cumulative Operation

Time at 1st to 4th Most

Recent Fault

Displays the cumulative operation time when the first to the fourth most

recent faults occurred.

No signal output

available

1 h

U3-15 to

U3-20

(80E to

813)

Cumulative Operation

Time at 5th to 10th Most

Recent Fault

Displays the cumulative operation time when the fifth to the tenth most

recent faults occurred.

No signal output

available

1 h

U3-21

(300B)

Date Year at Most Recent

Fault

Displays the year when the most recent fault occurred.

No signal output

available

U3-22

(300C)

Date Month and Day at

Most Recent Fault

Displays the date and day when the most recent faults occurred.

No signal output

available

U3-23

(300D)

Time Hours and Minutes

at Most Recent Fault

Displays the time when the most recent fault occurred.

No signal output

available

U3-24

(300E)

Date Year at 2nd Most

Recent Fault

Displays the year when the second most recent fault occurred.

No signal output

available

U3-25

(300F)

Date Month and Day at

2nd Most Recent Fault

Displays the date and day when the second most recent fault occurred.

No signal output

available

U3-26

(3010)

Time Hours and Minutes

at 2nd Most Recent Fault Displays the time when the second most recent fault occurred.

No signal output

available

U3-27

(3011)

Date Year at 3rd Most

Recent Fault

Displays the year when the most third recent fault occurred.

No signal output

available

U3-28

(3012)

Date Month and Day at 3rd

Most Recent Fault

Displays the date and day when the third most recent fault occurred.

No signal output

available

U3-29

(3013)

Time Hours and Minutes

at 3rd Most Recent Fault Displays the time when the third most recent fault occurred.

No signal output

available

U3-30

(3014)

Date Year at 4th Most

Recent Fault

Displays the year when the fourth most recent fault occurred.

No signal output

available

U3-31

(3015)

Date Month and Day at 4th

Most Recent Fault

Displays the date and day when the fourth most recent fault occurred.

No signal output

available

U3-32

(3016

Time Hours and Minutes

at 4th Most Recent Fault Displays the time when the fourth most recent fault occurred.

No signal output

available

U3-33

(3017)

Date Year at 5th Most

Recent Fault

Displays the year when the fifth most recent fault occurred.

No signal output

available

U3-34

(3018)

Date Month and Day at 5th

Most Recent Fault

Displays the date and day when the fifth most recent fault occurred.

No signal output

available

U3-35

(3019)

Time Hours and Minutes

at 5th Most Recent Fault Displays the time when the fifth most recent fault occurred.

No signal output

available

U3-36

(301A)

Date Year at 6th Most

Recent Fault

Displays the year when the sixth most recent fault occurred.

No signal output

available

U3-37

(301B)

Date Month and Day a 6th

Most Recent Fault

Displays the date and day when the sixth most recent fault occurred.

No signal output

available

U3-38

(301C)

Time Hours and Minutes

at 6th Most Recent Fault Displays the time when the most sixth recent fault occurred.

No signal output

available

U3-39

(301D)

Date Year at 7th Most

Recent Fault

Displays the year when the most seventh recent fault occurred.

No signal output

available

U3-40

(301E)

Date Month and Day at 7th

Most Recent Fault

Displays the date and day when the seventh most recent fault occurred.

No signal output

available

B.13 U: Monitors

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

461

B

Parameter List

This manual is related to the following products: