Models 2A0004 to 2A0138, 4A0002 to 4A0072, and 5A0003 to 5A0052 come with a built-in braking transistor.

n

L8-78: Power Unit Output Phase Loss Protection

Protects the power unit from phase loss.

Note:

This parameter is only available in models 4A0930 and 4A1200.

No.

Name

Setting Range

Default

L8-78

Power Unit Output Phase Loss Protection

0, 1

1

Setting 0: Disabled
Setting 1: Enabled

n

L8-93: LSo Detection Time at Low Speed

Sets the amount of time until baseblock is executed after LSo has been detected at low speed.
A setting of 0.0 s disables this parameter.

No.

Name

Setting Range

Default

L8-93

LSo Detection Time at Low Speed

0.0 to 10.0 s

1.0 s

n

L8-94: LSo Detection Level at Low Speed

Determines the detection level of Sto at low speed. Set as a percentage of the maximum frequency (E1-04).

No.

Name

Setting Range

Default

L8-94

LSo Detection Level at Low Speed

0 to 10%

3%

n

L8-95: Average LSo Frequency at Low Speed

Sets the average number of times LSo can occur at low speed.

No.

Name

Setting Range

Default

L8-95

Average LSo Frequency at Low Speed

1 to 50 times

10 times

5.8 L: Protection Functions

262

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual