B.6 E: Motor Parameters

u

E1: V/f Pattern

No.

(Addr.

Hex)

Name

Description

Values

Page

E1-01

(300)

Input Voltage Setting

This parameter must be set to the power supply voltage.

WARNING!

Electrical Shock Hazard. Drive input voltage (not motor

voltage) must be set in E1-01 for the protective features of the drive to

function properly. Failure to do so may result in equipment damage

and/or death or personal injury.

Default: 230 V

<1>

Min.: 155
Max.: 255

<1>

190

E1-03

(302)

V/f Pattern Selection

0: 50 Hz, Constant torque 1

1: 60 Hz, Constant torque 2

2: 60 Hz, Constant torque 3 (50 Hz base)

3: 72 Hz, Constant torque 4 (60 Hz base)

4: 50 Hz, Variable torque 1

5: 50 Hz, Variable torque 2

6: 60 Hz, Variable torque 1

7: 60 Hz, Variable torque 2

8: 50 Hz, High starting torque 1

9: 50 Hz, High starting torque 2

A: 60 Hz, High starting torque 3

B: 60 Hz, High starting torque 4

C: 90 Hz (60 Hz base)

D: 120 Hz (60 Hz base)

E: 180 Hz (60 Hz base)

F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern

Default: F

<2>

Range: 0 to 9;

A to FF

190

E1-04

(303)

Maximum Output

Frequency

These parameters are only applicable when E1-03 is set to F.

To set linear V/f characteristics, set the same values for E1-07 and E1-09.

In this case, the setting for E1-08 will be disregarded. Ensure that the four

frequencies are set according to these rules:

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Output Voltage (V)

Frequency (Hz)

E1-05
E1-12

E1-13

E1-08

E1-10

E1-09

E1-07 E1-06 E1-11 E1-04

Default: 60.0 Hz

Min.: 40.0

Max.: 400.0

193

E1-05

(304)

Maximum Voltage

Default: 575 V

<1>

Min.: 0.0

Max.: 255.0

193

E1-06

(305)

Base Frequency

Default: 60.0 Hz

Min.: 0.0

Max.: E1-04

193

E1-07

(306)

Middle Output Frequency

Default: 3.0 Hz

Min.: 0.0

Max.: E1-04

193

E1-08

(307)

Middle Output Frequency

Voltage

Default: 15.0 V

<1>

Min.: 0.0 V

Max.: 255.0 V

193

E1-09

(308)

Minimum Output Frequency

Default: 1.5 Hz

Min.: 0.0

Max.: E1-04

193

E1-10

(309)

Minimum Output Frequency

Voltage

Default: 9.0 V

<1>

Min.: 0.0 V

Max.: 255.0 V

193

E1-11

(30A)

<4>

Middle Output Frequency 2

Default: 0.0 Hz

Min.: 0.0

Max.: E1-04

193

E1-12

(30B)

<4>

Middle Output Frequency

Voltage 2

Default: 0.0 V

Min.: 0.0
Max.: 255.0 V

<1>

193

E1-13

(30C)

Base Voltage

Default: 0.0 V

<3>

Min.: 0.0
Max.: 255.0 V

<1>

193

<1> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<4> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.