Setting B: Drive Overheat Alarm (oH2)

Triggers an oH2 alarm when the contact closes. Drive operation is not affected because this is an alarm.

Setting C: Analog Terminal Input Selection (Terminal A1, A2, A3)

When closed, the terminals specified in H3-14 are enabled. When open, the drive disregards the input signal to the analog

terminals.

Setting F: Through Mode

Select this setting when using the terminal in a pass-through mode. When set to F, an input does not trigger any function in

the drive. Setting F, however, still allows the input status to be read out by a PLC via a communication option or MEMOBUS/

Modbus communications.

Setting 10, 11: Up/Down Function

The Up/Down function allows the frequency reference to be set by two push buttons when one digital input is programmed

as the Up input (H1-oo= 10) to increase the frequency reference and the other digital input is programmed as the Down input

(H1-oo= 11) to decrease the frequency reference.
The Up/Down function takes priority over the frequency references from the digital operator, the analog inputs, and the pulse

input (b1-01 = 0, 1, 4). When using the Up/Down function, references provided by these sources will be disregarded.
The inputs operate as shown in

Table 5.30

:

Table 5.30 Up, Down Command

Status

Drive Operation

Up (10)

Down (11)

Open

Open

Hold current frequency reference

Closed

Open

Increase frequency reference

Open

Closed

Decrease frequency reference

Closed

Closed

Hold current frequency reference

Note:

1. An oPE03 alarm occurs when only one of the Up/Down functions is programmed to a digital input.
2. An oPE03 alarm occurs when the Up/Down function is assigned to the terminals and a different digital input is programmed for the

Accel/decel ramp hold function. For more information on alarms,

Refer to Drive Alarms, Faults, and Errors on page 292

.

3. The Up/Down function can only be used for External reference 1. Consider this when using Up/Down and the external reference switching

command (H1-oo = 2).

Using the Up/Down Function with Frequency Reference Hold (d4-01)
• If the frequency reference hold function is disabled (d4-01 = 0), the Up/Down frequency reference will be reset to 0 when

the Run command is cleared or the power is cycled.

• When d4-01 = 1, the drive will save the frequency reference set by the Up/Down function. When the Run command or the

power is cycled, the drive will restart with the saved reference value. Close the Up or Down input without an active Run

command to reset the saved value.

Refer to d4-01: Frequency Reference Hold Function Selection on page 185

.

Using the Up/Down Function with Frequency Reference Limits
Parameter d2-01 determines the upper frequency reference limit.
The value for the lower frequency reference limit depends on the parameter d4-10 setting. This value can be set by an analog

input or parameter d2-02.

Refer to d4-10: Up/Down Frequency Reference Limit Selection on page 188

for details. When a

Run command is applied, the lower limits function as follows:
• If the lower limit is set by d2-02 only, the drive accelerates to this limit as soon as a Run command is entered.
• If the lower limit is determined by an analog input only, the drive accelerates to the limit when both the Run command and

an Up or Down command are active. The drive will not start running if only the Run command is active.

• If the lower limit is set by both an analog input and d2-02, and the analog limit is higher than the d2-02 value, the drive

accelerates to the d2-02 value when a Run command is input. When the d2-02 value is reached, the drive accelerates to the

analog limit only if an Up or Down command is set.

Figure 5.39

shows an Up/Down function example with a lower frequency reference limit set by d2-02, and the frequency

reference hold function both enabled and disabled.

5.7 H: Terminal Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

207

5

Parameter Details