beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 438

background image

No.

(Addr.

Hex)

Name

Description

Values

Page

H3-05

(413)

Terminal A3 Signal Level

Selection

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A3 for a current or voltage

input signal.

Default: 0

Range: 0 to 3

225

H3-06

(414)

Terminal A3 Function

Selection

Sets the function of terminal A3.

Default: 2

Range: 0 to 26

225

H3-07

(415)

Terminal A3 Gain Setting

Sets the level of the input value selected in H3-06 when 10 V is input at

terminal A3.

Default: 100.0%

Min.: -999.9

Max.: 999.9

225

H3-08

(416)

Terminal A3 Bias Setting

Sets the level of the input value selected in H3-06 when 0 V is input at terminal

A3.

Default: 0.0%

Min.: -999.9

Max.: 999.9

225

H3-09

(417)

Terminal A2 Signal Level

Selection

0: 0 to 10 V

1: -10 to 10 V

2: 4 to 20 mA

3: 0 to 20 mA

Note:

Use Jumper S1 to set input terminal A2 for a current or voltage

input signal.

Default: 2

Range: 0 to 3

225

H3-10

(418)

Terminal A2 Function

Selection

Sets the function of terminal A2.

Default: 0

Range: 0 to 26

226

H3-11

(419)

Terminal A2 Gain Setting

Sets the level of the input value selected in H3-10 when 10 V (20 mA) is input

at terminal A2.

Default: 100.0%

Min.: -999.9

Max.: 999.9

226

H3-12

(41A)

Terminal A2 Bias Setting

Sets the level of the input value selected in H3-10 when 0 V (0 or 4 mA) is

input at terminal A2.

Default: 0.0%

Min.: -999.9

Max.: 999.9

226

H3-13

(41B)

Analog Input Filter Time

Constant

Sets a primary delay filter time constant for terminals A1, A2, and A3. Used

for noise filtering.

Default: 0.03 s

Min.: 0.00

Max.: 2.00

226

H3-14

(41C)

Analog Input Terminal

Enable Selection

Determines which analog input terminals will be enabled when a digital input

programmed for “Analog input enable” (H1-oo = C) is activated.

1: Terminal A1 only

2: Terminal A2 only

3: Terminals A1 and A2 only

4: Terminal A3 only

5: Terminals A1 and A3

6: Terminals A2 and A3

7: All terminals enabled

Default: 7

Range: 1 to 7

226

H3-16

(2F0)

Terminal A1 Offset

Adds an offset when the analog signal to terminal A1 is at 0 V.

Default: 0

Min.: -500

Max.: 500

226

H3-17

(2F1)

Terminal A2 Offset

Adds an offset when the analog signal to terminal A2 is at 0 V.

Default: 0

Min.: -500

Max.: 500

226

H3-18

(2F2)

Terminal A3 Offset

Adds an offset when the analog signal to terminal A3 is at 0 V.

Default: 0

Min.: -500

Max.: 500

226

H3 Multi-Function Analog Input Settings

H3-oo

Setting

Function

Description

Page

0

Frequency bias

10 V = E1-04 (maximum output frequency)

227

1

Frequency gain

0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting of -100

to 0%.

227

2

Auxiliary frequency reference 1

10 V = E1-04 (maximum output frequency)

227

3

Auxiliary frequency reference 2

10 V = E1-04 (maximum output frequency)

227

4

Output voltage bias

10 V = E1-05 (motor rated voltage)

227

5

Accel/decel time gain

10 V = 100%

227

B.7 H Parameters: Multi-Function Terminals

438

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: