Setting 1: Enabled (6 Hz and above)

Slip compensation is enabled during regenerative operation. It will not be active at output frequencies below 6 Hz.

Setting 2: Enabled (compensation provided wherever possible)

Slip compensation is enabled during regenerative operation and at frequencies as low as 2 Hz. The drive uses the motor rated

slip set to E2-02 to automatically calculate the frequency range where compensation will be disabled.

u

C4: Torque Compensation

The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.

Note:

Set the motor parameters and V/f pattern properly before setting torque compensation parameters.

n

C4-01: Torque Compensation Gain

Sets the gain for the torque compensation function.

No.

Parameter Name

Setting Range

Default

C4-01

Torque Compensation Gain

0.00 to 2.50

1.00

n

C4-02: Torque Compensation Primary Delay Time 1

Sets the delay time used for applying torque compensation.

No.

Parameter Name

Setting Range

Default

C4-02

Torque Compensation Primary Delay Time 1

0 to 60000 ms

200 ms

u

C6: Carrier Frequency

n

C6-02: Carrier Frequency Selection

Sets the switching frequency of the drive output transistors. Changes to the switching frequency lower audible noise and reduce

leakage current.

No.

Parameter Name

Setting Range

Default

C6-02

Carrier Frequency Selection

1 to 9; A, F

<1>

7

<1> The setting range is 1, 2, and F for models 4A0930 and 4A1200

Settings:

C6-02

Carrier Frequency

C6-02

Carrier Frequency

C6-02

Carrier Frequency

1

2.0 kHz

5

12.5 kHz

9

Swing PWM 3

2

5.0 kHz

6

15.0 kHz

A

Swing PWM 4

3

8.0 kHz

7

Swing PWM 1

B to E:

No setting possible

4

10.0 kHz

8

Swing PWM 2

F

User defined (C6-03 to C6-05)

Note:

Swing PWM uses a carrier frequency of 2.0 kHz as a base, then applies a special PWM pattern to reduce the audible noise.

Guidelines for Carrier Frequency Parameter Setup

Symptom

Remedy

Speed and torque are unstable at low speeds

Lower the carrier frequency.

Noise from the drive affects peripheral devices
Excessive leakage current from the drive
Wiring between the drive and motor is too long

<1>

Audible motor noise is too loud

Increase the carrier frequency or use Swing PWM.

<2>

<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to

Table 5.14

.

<2> The default carrier frequency is Swing PWM (C6-02 = 7), using a 2 kHz base. Increasing the carrier frequency is permissible , however the drive

rated current is reduced when the carrier frequency is increased.

Table 5.14 Wiring Distance and Carrier Frequency

Wiring Distance

Up to 50 m

Up to 100 m

Greater than 100 m

Recommended setting value for C6-02

1 to F (up to 15 kHz)

1 to 2 (up to 5 kHz),

7 (Swing PWM)

1 (up to 2 kHz), 7 (Swing PWM)