beautypg.com

Auto-tuning interruption and fault codes, Auto-tuning operation example, Selecting the type of auto-tuning – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 130: 7 auto-tuning

background image

n

Notes on Rotational Auto-Tuning

• Decouple the load from the motor to achieve optimal performance from Rotational Auto-Tuning. Rotational Auto-Tuning

is best suited for applications requiring high performance over a wide speed range.

• If it is not possible to decouple the motor and load, reduce the load so it is less than 30% of the rated load. Performing

Rotational Auto-Tuning with a higher load will set motor parameters incorrectly, and can cause irregular motor rotation.

• Ensure the motor-mounted brake is fully released, if installed.
• Connected machinery should be allowed to rotate the motor.

n

Notes on Stationary Auto-Tuning

Stationary Auto-Tuning modes analyze motor characteristics by injecting current into the motor for approximately one minute.

WARNING!

Electrical Shock Hazard. When executing stationary Auto-Tuning, voltage is applied to the motor before the motor rotates. Do

not touch the motor until Auto-Tuning is completed. Failure to comply may result in injury or death from electrical shock.
WARNING!

Sudden Movement Hazard. If installed, do not release the mechanical brake during Stationary Auto-Tuning. Inadvertent brake

release may cause damage to equipment or injury to personnel. Ensure that the mechanical brake release circuit is not controlled by the

drive multi-function digital outputs.

u

Auto-Tuning Interruption and Fault Codes

If tuning results are abnormal or the STOP key is pressed before completion, Auto-Tuning will be interrupted and a fault code

will appear on the digital operator.

B

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

A

LO

RE

ESC

RUN

STOP

ENTER

RESET

DIGITAL OPERATOR JVOP-180

ALM

ALM

- A.TUNE -

X.XX Hz/ X.XXA

DRV

Tune Proceeding

Rdy

FWD

<

<<

<<< >>>

>>

>

- MODE -

Er-03

STOP key

DRV

FWD

RESET

A – During Auto-Tuning

B – Auto-Tuning Aborted

Figure 4.10 Auto-Tuning Aborted Display

u

Auto-Tuning Operation Example

The following example demonstrates Stationary Auto-Tuning for Line-to-Line Resistance.

n

Selecting the Type of Auto-Tuning

Step

Display/Result

1. Turn on the power to the drive. The initial display appears.

- MODE -

U1-01= 0.00Hz
U1-02= 0.00Hz

U1-03= 0.00A

DRV

FREF (OPR)

Rdy

JOG

FWD

FWD/REV

LSEQ

LREF

2. Press

or

until the Auto-Tuning display appears.

HELP

- MODE -

PRG

Auto-Tuning

DATA

AUTO

FWD

3. Press

to begin setting parameters.

- A.TUNE -

T1-

01

= 2

*2*

Term Resistance

PRG

Tuning Mode Sel

Rdy

ESC

FWD

DATA

4. Press

to display the value for T1-01.

- A.TUNE -

T1-01=

2

*2*

Term Resistance

PRG

Tuning Mode Sel

Rdy

FWD

“2”

4.7 Auto-Tuning

130

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

This manual is related to the following products: