beautypg.com

Refer to multi-function analog, For a list of functions and descriptions – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 227

background image

No.

Name

Setting Range

Default

H3-16

Terminal A1 Offset

-500 to 500

0

H3-17

Terminal A2 Offset

-500 to 500

0

H3-18

Terminal A3 Offset

-500 to 500

0

n

Multi-Function Analog Input Terminal Settings

See

Table 5.34

for information on how H3-02, H3-10, and H3-06 determine functions for terminals A1, A2, and A3.

Note:

The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting

and adjusting analog input functions.

Table 5.34 Multi-Function Analog Input Terminal Settings

Setting

Function

Page

0

Frequency Bias

227

1

Frequency Gain

227

2

Auxiliary Frequency Reference 1

227

3

Auxiliary Frequency Reference 2

227

4

Output Voltage Bias

227

5

Accel/Decel Time Gain

227

6

DC Injection Braking Current

228

7

Torque Detection Level

228

8

Stall Prevention Level During Run

228

9

Output Frequency Lower Limit Level

228

Setting

Function

Page

B

PID Feedback

228

C

PID Setpoint

228

D

Frequency Bias

228

E

Motor Temperature (PTC Input)

229

16

Differential PID Feedback

229

17

<1>

Motor Thermistor (NTC)

229

1F

Through Mode

229

25

Secondary PI Setpoint

229

26

Secondary PI Feedback

229

<1> This function is only available in models 4A0930 and 4A1200.

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency

reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also

when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference

by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input

terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.

Setting 1: Frequency Gain

The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog

input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.

Setting 2: Auxiliary Reference 1

Sets the auxiliary frequency reference 1 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 181

for details.

Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 181

for details.

Setting 4: Output Voltage Bias

Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available

only when using V/f Control.

Setting 5: Accel/Decel Time Gain

Adjusts the gain level for the acceleration and deceleration times set to parameters C1-01 through C1-04.
The drive acceleration time is calculated by multiplying the gain level to C1-oo as follows:
C1-oo × Accel/decel time gain = Drive accel/decel time

5.7 H: Terminal Functions

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

227

5

Parameter Details

This manual is related to the following products: