Multi-function input

PTC
thermistor

A3 (0-10 V)

AC

V+ Power supply
+10.5 Vdc,
max. 20 mA

12 kOhm
resistor

PTC external circuit
(customer supplied)

Figure 5.67 Connection of a Motor PTC

The PTC must exhibit the characteristics shown in

Figure 5.68

in one motor phase. The motor overload protection of the drive

expects 3 of these PTCs to be connected in a series.

Resistance ( )

Class F
150 ºC

Class H
180 ºC

Tr: threshold value

Temperature

Tr’

Tr + 5K (oH4 Fault Level)

Tr

Tr - 5K (oH3 Alarm Level)

Figure 5.68 Motor PTC Characteristics

Set up overheat detection using a PTC using parameters L1-03, L1-04, and L1-05 as explained in the following sections.

n

L1-03: Motor Overheat Alarm Operation Selection (PTC input)

Sets the drive operation when the PTC input signal reaches the motor overheat alarm level (oH3).

No.

Name

Setting Range

Default

L1-03

Motor Overheat Alarm Operation Selection (PTC input)

0 to 3

3

Setting 0: Ramp to Stop

The drive stops the motor using the deceleration time 1 set in parameter C1-02.

Setting 1: Coast to Stop

The drive output is switched off and the motor coasts to stop.

Setting 2: Fast Stop

The drive stops the motor using the Fast Stop time set in parameter C1-09.

Setting 3: Alarm Only

The operation is continued and an oH3 alarm is displayed on the digital operator.

n

L1-04: Motor Overheat Fault Operation Selection (PTC input)

Sets the drive operation when the PTC input signal reaches the motor overheat fault level (oH4).

5.8 L: Protection Functions