Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 509

Register No.
Contents
00E0H
oFb3x Contents (CN5-B)
bit 0
Comm. ID Error (oFb30)
bit 1
Model Code Error (oFb31)
bit 2
Sumcheck Error (oFb32)
bit 3
Comm. option timeout waiting for response (oFb33)
bit 4
MEMOBUS Timeout (oFb34)
bit 5
Drive timeout waiting for response (oFb35)
bit 6
CI Check Error (oFb36)
bit 7
Drive timeout waiting for response (oFb37)
bit 8
Control Command Selection Error (oFb38)
bit 9
Drive timeout waiting for response (oFb39)
bit A
Control Response Selection 1 Error (oFb40)
bit B
Drive timeout waiting for response (oFb41)
bit C
Control Response Selection 2 Error (oFb42)
bit D
Control Response Selection Error (oFb43)
bit E, F
Reserved
00E1H
oFC0x Contents (CN5-C)
bit 0
Option compatibility error (oFC00)
bit 1
Option not properly connected (oFC01)
bit 2
Same type of option card already connected (oFC02)
bit 3, 4
Reserved
bit 5
A/D Conversion Fault (oFC05)
bit 6
Option Response Error (oFC06)
bit 7 to F
Reserved
00E2H
oFC1x Contents (CN5-C)
bit 0
Option RAM Fault (oFC10)
bit 1
Option Operation Mode Fault (SLMOD) (oFC11)
bit 2
Drive Receive CRC Error (oFC12)
bit 3
Drive Receive Frame Error (oFC13)
bit 4
Drive Receive Abort Error (oFC14)
bit 5
Option Receive CRC Error (oFC15)
bit 6
Option Receive Frame Error (oFC16)
bit 7
Option Receive Abort Error (oFC17)
bit 8 to F
Reserved
00E3H, 00E4H
Reserved
C.9 MEMOBUS/Modbus Data Table
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
509
C
MEMOBUS/Modbus Communications