beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 508

background image

Register No.

Contents

00DBH

oFA3x Contents (CN5-A)
bit 0

Comm. ID Error (oFA30)

bit 1

Model Code Error (oFA31)

bit 2

Sumcheck Error (oFA32)

bit 3

Comm. option timeout waiting for response (oFA33)

bit 4

MEMOBUS Timeout (oFA34)

bit 5

Drive timeout waiting for response (oFA35)

bit 6

CI Check Error (oFA36)

bit 7

Drive timeout waiting for response (oFA37)

bit 8

Control Command Selection Error (oFA38)

bit 9

Drive timeout waiting for response (oFA39)

bit A

Control Response Selection 1 Error (oFA40)

bit B

Drive timeout waiting for response (oFA41)

bit C

Control Response Selection 2 Error (oFA42)

bit D

Control Response Selection Error (oFA43)

bit E, F

Reserved

00DCH

oFb0x Contents (CN5-B)
bit 0

Option compatibility error (oFb00)

bit 1

Option not properly connected (oFb01)

bit 2

Same type of option card already connected (oFb02)

bit 3, 4

Reserved

bit 5

A/D Conversion Fault (oFb05)

bit 6

Option Response Error (oFb06)

bit 7 to F

Reserved

00DDH

oFb1x Contents (CN5-B)
bit 0

Option RAM Fault (oFb10)

bit 1

Option Operation Mode Fault (SLMOD) (oFb11)

bit 2

Drive Receive CRC Error (oFb12)

bit 3

Drive Receive Frame Error (oFb13)

bit 4

Drive Receive Abort Error (oFb14)

bit 5

Option Receive CRC Error (oFb15)

bit 6

Option Receive Frame Error (oFb16)

bit 7

Option Receive Abort Error (oFb17)

bit 8 to F

Reserved

00DEH to 00DFH

Reserved

C.9 MEMOBUS/Modbus Data Table

508

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual