n

L5-02: Auto Restart Fault Output Operation Selection

Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.

No.

Name

Setting Range

Default

L5-02

Auto Restart Fault Output Operation Selection

0, 1

0

Setting 0: No Fault Output

Auto-Restart - Cancel Early
Fault output disabled (L5-02 = 0)

Run command

Fault condition

Fault display

Fault digital output

Output Frequency

(U1-02)

L5-04

Figure 5.81 Auto Restart Cancel Early

Setting 1: Fault Output Is Set

n

L5-04: Fault Reset Interval Time

Determines the amount of time to wait between restart attempts when parameter L5-05 is set to 1.

No.

Name

Setting Range

Default

L5-04

Fault Reset Interval Time

0.5 to 600.0 s

10.0 s

n

L5-05: Fault Reset Operation Selection

No.

Name

Setting Range

Default

L5-05

Fault Reset Operation Selection

0, 1

0

Setting 0: Count Successful Restarts

The drive will continuously attempt to restart. If it restarts successfully, the restart counter is increased. This operation is

repeated each time a fault occurs until the counter reaches the value set to L5-01.

Setting 1: Count Restart Attempts

The drive will attempt to restart using the time interval set to parameter L5-04. A record is kept of the number of attempts to

restart to the drive, regardless of whether those attempts were successful. When the number of attempted restarts exceeds the

value set to L5-01, the drive stops attempting to restart.

u

L6: Torque Detection

The drive provides two independent torque detection functions that trigger an alarm or fault signal when the load is too heavy

(oL), or suddenly drops (UL). These functions are set up using the L6-oo parameters. Program the digital outputs as shown

below to indicate the underload or overload condition to an external device:

Note:

When overtorque occurs in the application, the drive may stop due to overcurrent (oC) or overload (oL1). To prevent the drive from stopping,

use torque detection to indicate an overload situation to the controller before oC or oL1 occur. Use undertorque detection to discover

application problems like a torn belt, a pump shutting off, or other similar trouble.

5.8 L: Protection Functions

254

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual