5.4 d: Reference Settings

The figure below gives an overview of the reference input, selections, and priorities.

MS 2

Terminal A2

Digital Input
H1-oo = 2

Terminal A3

d1-03

H3-06 = 3

H3-06 = 3

Terminal A1/A2/A3

Frequency

Reference

Remote

Set to supply the

auxiliary frequency reference

Local

MEMOBUS comm.

d1-01

(Freq.Ref 1)

b1-01

(Freq. Reference Source 1)

Pulse Train Input

=3

=2

=1

=0

=4

Option Card

MEMOBUS comm.

d1-01

(Freq. Ref. 1)

Pulse Train Input

=3

=2

=1

=0

=4

Option card

Frequency

Reference

4 through 16

Jog Frequency

Multi-Step Speed

NetRef

ComRef

d1-04

d1-15

d1-16

d1-17

Terminal A1/A2/A3

d1-02

0

1

Memobus Register 0001h, bit 4 if
standard 2 wire sequence selected,
usually 0

Set from Communications
Option Card, usually 0

0

1

0

1

b1-15

(Freq. Reference Source 2)

H3-10 = 2

H3-10 = 2

MS 1

MS 3

MS 4

MS 15

MS 16

Jog

Open

Close

LO/RE Key on Digital Operator or

Digital Input H1-oo = 1

Digital Input (H1-oo)
Jog Reference (=6),
FJOG(=12), RJOG(=13)

Figure 5.26 Frequency Reference Setting Hierarchy

u

d1: Frequency Reference

n

d1-01 to d1-17: Frequency Reference 1 to 16 and Jog Frequency Reference

The drive lets the user switch between up to 17 preset frequency references during run (including the Jog reference) through

the digital input terminals. The drive uses the acceleration and deceleration times that have been selected when switching

between each frequency reference.
The Jog frequency overrides all other frequency references and must be selected by a separate digital input.
The multi-speed references 1, 2, and 3 can be provided by analog inputs.

No.

Parameter Name

Setting Range

Default

d1-01 to d1-16

Frequency Reference 1 to 16

0.00 to 400.00 Hz

<1>

0.00 Hz

d1-17

Jog Frequency Reference

0.00 to 400.00 Hz

<1>

6.00 Hz

<1> The upper limit is determined by the maximum output frequency (E1-04) and upper limit for the frequency reference (d2-01).

Multi-Step Speed Selection

To use several speed references for a multi-step speed sequence, set the H1-oo parameters to 3, 4, 5, and 32. To assign the

Jog reference to a digital input, set H1-oo to 6.
Notes on using analog inputs as Multi-Speed 1, 2, and 3:
Multi-Step Speed 1

Set b1-01 to 1 to set terminal A1 analog input to Multi-Step Speed 1.
Set b1-01 to 0 when setting d1-01, Frequency Reference 1, to Multi-Step Speed 1.

Multi-Step Speed 2

Set H3-06, Terminal A3 Function Selection, to 2 (Auxiliary Frequency Reference 1) when setting terminal A3 analog input

to Multi-Step Speed 2.