Setting 2: External Reference 1/2 Selection

This function switches the Run command and frequency reference source between External reference 1 and 2 if the drive is

in the REMOTE mode.

Status

Description

Open

External reference 1 is used (defined by parameters b1-01 and b1-02)

Closed

External reference 2 is used (defined by parameters b1-15 and b1-16)

Note:

Default drive settings do not allow switching between External reference 1 and 2 during run.

Refer to b1-07: LOCAL/REMOTE Run

Selection on page 151

if this feature is required by the application.

Setting 3 to 5: Multi-Step Speed Reference 1 to 3

Switches multi-step speed frequency references d1-01 to d1-08 by digital inputs.

Refer to d1: Frequency Reference on page

181

for details.

Setting 6: Jog Reference Selection

The Jog frequency set in parameter d1-17 becomes the frequency reference when the input terminal closes.

Refer to d1:

Frequency Reference on page 181

for details.

Setting 7: Accel/Decel Time Selection 1

Switches between accel/decel times 1 (C1-01 and C1-02) and 2 (C1-03 and C1-04).

Refer to C1-01 to C1-04: Accel, Decel

Times 1 and 2 on page 176

for details.

Setting 8, 9: Baseblock Command (N.O., N.C.)

When the drive receives a baseblock command, the output transistors stop switching, the motor coasts to stop, and a bb alarm

flashes on the digital operator to indicate baseblock. When baseblock ends while a Run command is active, the drive performs

Speed Search to restart the motor.

DIgital Input Function

Drive Operation

Input Open

Input Closed

Setting 8 (N.C.)

Baseblock (Interrupt output)

Normal operation

Setting 9 (N.O.)

Normal operation

Baseblock (Interrupt output)

WARNING!

Sudden Movement Hazard. When using a mechanical holding brake with the drive in a lifting application, close the brake when

the drive output is cut off by a baseblock command triggered by one of the input terminals. Failure to comply will result in a slipping load

from the motor suddenly coasting when the baseblock command is entered and may cause serious injury or death.

Begin Speed Search from the
previous frequency reference

Run command

Baseblock input

Frequency
reference

Output frequency

OFF

ON

Output off, motor coasts

ON

Baseblock

release

Figure 5.38 Baseblock Operation During Run

Setting A: Accel/Decel Ramp Hold

When the digital input programmed for the Accel/decel ramp hold function closes, the drive locks (holds) the output frequency.

Acceleration or deceleration resumes when the input is reopened.
If the Accel/decel ramp hold function is enabled (d4-01 = 1), the drive saves the output frequency to memory when the Ramp

Hold input is closed. When the drive is restarted after stop or after power supply interruption, the saved output frequency

becomes the frequency reference (provided that the Accel/decel ramp hold input is still closed).

Refer to d4-01: Frequency

Reference Hold Function Selection on page 185

for details.