Notes on Using High Slip Braking

• The set deceleration time is ignored during HSB. Use Overexcitation Deceleration 1 (L3-04 = 4) to stop the motor within a

specified time.

• Braking time varies based on the load inertia and motor characteristics.
• Enabling HSB and KEB Ride-Thru simultaneously will trigger an oPE03 error.
• HSB must be triggered by a digital input set to H1-oo = 68. After the HSB command is given, the drive will not restart

until the motor is completely stopped and the Run command is cycled.

• Use parameters n3-01 through n3-04 to adjust HSB.

n

n3-01: High Slip Braking Deceleration Frequency Width

Sets the step width for frequency reduction during HSB. Increase n3-01 if DC bus overvoltage (ov) occurs during HSB.

No.

Name

Setting Range

Default

n3-01

High Slip Braking Deceleration Frequency Width

1 to 20%

5%

n

n3-02: High Slip Braking Current Limit

Sets the maximum current to be output during an HSB stop as a percentage of motor rated current (E2-01). Reducing the

current limit increases the deceleration time. This value must not exceed the drive overload capacity.
• Lower this setting if overvoltage occurs during HSB.
• Lower this setting if motor current is too high during HSB. High current can damage the motor due to overheat.
• The default setting is 120% when the drive is set for Normal Duty.

No.

Name

Setting Range

Default

n3-02

High Slip Braking Current Limit

100 to 200%

Determined by

L8-38

n

n3-03: High Slip Braking Dwell Time at Stop

When the motor reaches a relatively low speed at the end of HSB, the output frequency is kept at the minimum output frequency

set to E1-09 for the time set to n3-03. Increase this time if the inertia is very high and the motor coasts after HSB is complete.

No.

Name

Setting Range

Default

n3-03

High Slip Braking Dwell Time at Stop

0.0 to 10.0 s

1.0 s

n

n3-04: High Slip Braking Overload Time

Sets the time required for an HSB overload fault (oL7) to occur when the drive output frequency does not change during an

HSB stop due to excessive load inertia or the load rotating the motor. To protect the motor from overheat, the drive trips with

an oL7 fault if these conditions last longer than the time set in n3-04.

No.

Name

Setting Range

Default

n3-04

High Slip Braking Overload Time

30 to 1200 s

40 s

n

Overexcitation Deceleration (Induction Motors)

Increases the flux during deceleration and allows shorter deceleration time settings without the use of a braking resistor.

Enabled by setting L3-04 to 4 or 5.

Refer to L3-04: Stall Prevention Selection during Deceleration on page 248

.

Notes on Overexcitation Deceleration

• Frequently applying Overexcitation Deceleration raises the motor temperature because regenerative energy is mainly

dissipated as heat in the motor. In cases where frequent application is required, make sure the motor temperature does not

exceed the maximum allowable value or consider using a braking resistor option in lieu of Overexcitation Deceleration.

• During Overexcitation Deceleration 2, Hunting Prevention in V/f Control is disabled.
• Do not use Overexcitation Deceleration in combination with a braking resistor option.

Parameter Adjustments

• Use parameters n3-13 through n3-23 to adjust Overexcitation Deceleration.
• When repetitive or long Overexcitation Deceleration causes motor overheat, lower the overexcitation gain (n3-13) and reduce

the overslip suppression current level (n3-21).

• During Overexcitation Deceleration 1 (L3-04 = 4), the drive decelerates at the active deceleration time (C1-02 and C1-04).

Set this time so no overvoltage (ov) fault occurs.