4.7 Auto-Tuning

u

Types of Auto-Tuning

The drive offers different types of Auto-Tuning for induction motors. Refer to the tables below to select the type of Auto-

Tuning that bests suits the application.

Refer to Start-Up Flowchart on page 124

for directions on executing Auto-Tuning.

n

Auto-Tuning for Induction Motors

This feature automatically sets the V/f pattern and motor parameters E1-oo and E2-oo for an induction motor.

Table 4.12 Types of Auto-Tuning for Induction Motors

Type

Setting

Application Conditions and Benefits

Stationary Auto-Tuning for Line-to-

Line Resistance

T1-01 = 2

• The drive is used in V/f Control and other Auto-Tuning selections are not possible.
• Perform when entering motor data manually while using motor cables longer than 50

m.

• Drive and motor capacities differ.
• Tunes the drive after the cable between the drive and motor has been replaced with a

cable over 50 m long. Assumes Auto-Tuning has already been performed.

Rotational Auto-Tuning for V/f

Control

T1-01 = 3

• Recommended for applications using Speed Estimation Speed Search or using the

Energy Saving function in V/f Control.

• Assumes motor can rotate while Auto-Tuning is executed. Increases accuracy for

certain functions like torque compensation, slip compensation, Energy Saving, and

Speed Search.

Table 4.13

lists the data that must be entered for Auto-Tuning. Make sure this data is available before starting Auto-Tuning.

The necessary information is usually listed on the motor nameplate or in the motor test report provided by the motor

manufacturer.

Refer to Start-Up Flowchart on page 124

for details on the Auto-Tuning process.

Table 4.13 Auto-Tuning Input Data

Input Value

Input Parameter

Unit

Tuning Type (T1-01)

2

Line-to-Line Resistance

3

Rotational for V/f Control

Motor rated power

T1-02

kW

YES

YES

Motor rated voltage

T1-03

Vac

YES

Motor rated current

T1-04

A

YES

YES

Motor rated frequency

T1-05

Hz

YES

Number of motor poles

T1-06

-

YES

Motor rated Speed

T1-07

r/min

YES

Motor iron loss

T1-11

W

YES

u

Before Auto-Tuning the Drive

Check the items below before Auto-Tuning the drive.

n

Basic Auto-Tuning Preparations

• Auto-Tuning requires the user to input data from the motor nameplate or motor test report. Make sure this data is available

before Auto-Tuning the drive.

• For best performance, the drive input supply voltage must be at least equal to or greater than the motor rated voltage.

Note:

Better performance is possible when using a motor with a base voltage that is lower than the input supply voltage (20 V for 200 V class

models, 40 V for 400 V class models, and 60 V for 600 V class models). This is particularly important when operating the motor above

90% of base speed, where high torque precision is required.

• To cancel Auto-Tuning, press the STOP key on the digital operator.
• When using a motor contactor, make sure it is closed throughout the Auto-Tuning process.

Table 4.14

describes digital input and output terminal operation while Auto-Tuning is executed.

Table 4.14 Auto-Tuning Input Data

Motor Type

Auto-Tuning Type

Digital Input

Digital Output

IM Motor

Stationary Auto-Tuning for Line-to-Line Resistance

Digital input functions

are disabled.

Digital output functions are disabled.

Rotational Auto-Tuning for V/f Control

Functions the same as during normal operation

4.7 Auto-Tuning

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

129

4

Start-Up Programming & Operation