Table 5.35 KEB Function Related Adjustments

Parameter

Name

Setting Instructions

KEB Mode (L2-29)

0

1

2

3

C1-09

Fast Stop Time

• Increase if an overvoltage fault occurs during KEB deceleration.
• Decrease if an undervoltage fault occurs during KEB deceleration.

YES NO NO NO

C2-03

S-Curve at Deceleration

Start

• Shorten if undervoltage occurs immediately after KEB Ride-Thru is

triggered.

• Lengthen this setting if overvoltage occurs immediately after KEB

operation starts.

YES NO YES YES

L2-05

Undervoltage Detection

Level

Increase if an undervoltage fault occurs at KEB operation start to let the

drive detect power loss more quickly.

YES YES YES YES

L2-06

KEB Deceleration Time

• Increase if an overvoltage fault occurs during KEB deceleration
• Decrease if an undervoltage fault occurs during KEB deceleration

NO NO YES YES

L2-07

KEB Acceleration Time Adjust to the desired acceleration time. If set to 0, standard acceleration

times are used (C1-01, C1-03, C1-05, C1-07).

YES YES YES YES

L2-08

Frequency Gain at KEB

Start

• Increase if an undervoltage fault occurs immediately after KEB

operation starts.

• Decrease if an overvoltage fault occurs immediately after KEB

operation starts.

YES NO YES YES

L2-10

KEB Detection Time

• Increase when a digital input is set for KEB Ride-Thru and an

undervoltage fault occurs after power was lost because the device

controlling the input does not react quickly enough.

• If the DC bus voltage overshoots after KEB Ride-Thru begins (and

no input terminal is set to KEB Ride-Thru), increase L2-10 to longer

than the overshoot.

YES YES YES YES

L2-11

Desired DC Bus Voltage

during KEB

• Set to approximately 1.22 times the input voltage for Single Drive

KEB Ride-Thru 2.

• Set to approximately 1.4 times the input voltage for Single Drive KEB

Ride-Thru 1 and System KEB Ride-Thru modes.

YES YES YES YES

L3-20

Main Circuit Adjustment

Gain

• Increase this setting in steps of 0.1 if overvoltage or undervoltage

occurs at the beginning of deceleration

• Reduce if torque ripple occurs during deceleration while executing

KEB Ride-Thru.

NO YES NO NO

L3-21

Accel/Decel Rate

Calculation Gain

• Reduce L3-21 in steps of 0.05 if there is a fairly large speed or current

ripple.

• Decreasing this setting too much can cause a slow DC bus voltage

control response, and may lead to problems with overvoltage or

undervoltage.

NO YES NO NO

L3-24

Motor Acceleration Time Set the motor acceleration time as described on page

251

.

NO YES NO NO

L3-25

Load Inertia Ratio

Set the load/inertia ratio as described on page

251

.

NO YES NO NO

n

L2-02: Momentary Power Loss Ride-Thru Time

Sets the maximum time allowed to ride through a power loss. If power loss operation exceeds this time, the drive will attempt

to accelerate back to the frequency reference. This parameter is valid if L2-01 = 1 or 3.

Note:

The amount of time the drive is capable of recovering after a power loss is determined by the capacity of the drive. Drive capacity determines

the upper limit for L2-02.

No.

Name

Setting Range

Default

L2-02

Momentary Power Loss Ride-Thru Time

0.0 to 25.5 s

Determined by o2-04

n

L2-03: Momentary Power Loss Minimum Baseblock Time

Sets the minimum baseblock time when power is restored following a momentary power loss. This determines the time the

drive waits for the residual voltage in the motor to dissipate. Increase this setting if overcurrent or overvoltage occurs at the

beginning of Speed Search, after a power loss, or during DC Injection Braking.

No.

Name

Setting Range

Default

L2-03

Momentary Power Loss Minimum Baseblock Time

0.1 to 5.0 s

Determined by o2-04

5.8 L: Protection Functions

244