Terminal am/fm signal selection, Memobus/modbus termination, Refer to terminal am/fm – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 101: Refer to memobus, Table 3.14, 10 control i/o connections

Table 3.14 Voltage/Current Selection Parameter Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H3-01
Terminal A1 signal level selection
Selects the signal level for terminal A1.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
0
H3-05
Terminal A3 signal level selection
Selects the signal level for terminal A3.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
0
H3-09
Terminal A2 signal level selection
Selects the signal level for terminal A2.
0: 0 to 10 Vdc
1: 0 to 10 Vdc Bipolar
2: 4 to 20 mA
3: 0 to 20 mA
0 to 3
2
u
Terminal AM/FM Signal Selection
The signal type for terminals AM and FM can be set to either voltage or current output using jumper S5 on the terminal board
as explained in
. When changing the setting of jumper S5, parameters H4-07 and H4-08 must be set accordingly.
The default selection is voltage output for both terminals.
Refer to Switches and Jumpers on the Terminal Board on page
Table 3.15 Jumper S5 Settings
Terminal
Voltage Output
Current Output
Terminal AM
AM
FM
V
I
AM
FM
V
I
Terminal FM
AM
FM
V
I
AM
FM
V
I
Table 3.16 Parameter H4-07 and H4-08 Details
No.
Parameter Name
Description
Setting
Range
Default
Setting
H4-07
Terminal AM signal level selection
0: 0 to 10 Vdc
1: -10 to 10 Vdc
2: 4 to 20 mA
0 to 2
0
H4-08
Terminal FM signal level selection
u
MEMOBUS/Modbus Termination
This drive is equipped with a built-in termination resistor for the RS-422/485 communication port. DIP switch S2 enables or
disabled the termination resistor as shown in
. The OFF position is the default. The termination resistor should be
placed to the ON position when the drive is the last in a series of slave drives.
Refer to Switches and Jumpers on the Terminal
Table 3.17 MEMOBUS/Modbus Switch Settings
S2 Position
Description
ON
Internal termination resistor ON
OFF
Internal termination resistor OFF (default setting)
Note:
Refer to MEMOBUS/Modbus Communications on page 483
for details on MEMOBUS/Modbus.