D6: field weakening and field forcing – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 426

background image

No.

(Addr.

Hex)

Name

Description

Values

Page

d4-05

(2AC)

Frequency Reference Bias

Operation Mode Selection

(Up/Down 2)

0: Bias value is held if no input Up 2 or Down 2 is active.

1: When the Up 2 reference and Down 2 reference are both on or both off, the

applied bias becomes 0. The specified accel/decel times are used for

acceleration or deceleration.

Default: 0

Range: 0, 1

187

d4-06

(2AD)

Frequency Reference Bias

(Up/Down 2)

The Up/Down 2 bias value is saved in d4-06 when the frequency reference is

not input by the digital operator. Set as a percentage of the maximum output

frequency.

Default: 0.0%

Min.: -99.9

Max.: 100.0

188

d4-07

(2AE)

Analog Frequency

Reference Fluctuation Limit

(Up/Down 2)

Limits how much the frequency reference is allowed to change while an input

terminal set for Up 2 or Down 2 is enabled. If the frequency reference changes

for more than the set value, then the bias value is held and the drive accelerates

or decelerates to the frequency reference. Set as a percentage of the maximum

output frequency.

Default: 0.01%

Min.: 0.01

Max.: 100.0

188

d4-08

(2AF)

Frequency Reference Bias

Upper Limit (Up/Down 2)

Sets the upper limit for the bias and the value that can be saved in d4-06. Set

as a percentage of the maximum output frequency.

Default: 1.0%

Min.: 0.0

Max.: 100.0

188

d4-09

(2B0)

Frequency Reference Bias

Lower Limit (Up/Down 2)

Sets the lower limit for the bias and the value that can be saved in d4-06. Set

as a percentage of the maximum output frequency.

Default: 0.0%

Min.: -99.9

Max.: 0.0

188

d4-10

(2B6)

Up/Down Frequency

Reference Limit Selection

0: The lower limit is determined by d2-02 or an analog input.

1: The lower limit is determined by d2-02.

Default: 0

Range: 0, 1

188

u

d6: Field Weakening and Field Forcing

No.

(Addr

Hex.)

Name

Description

Values

Page

d6-01

(2A0)

Field Weakening Level

Sets the drive output voltage for the Field Weakening function as a percentage

of the maximum output voltage.

Enabled when a multi-function input is set for Field Weakening (H1-oo =

63).

Default: 80%

Min.: 0

Max.: 100

189

d6-02

(2A1)

Field Weakening Frequency

Limit

Sets the lower limit of the frequency range where Field Weakening control is

valid.

The Field Weakening command is valid only at frequencies above this setting

and only when the output frequency matches the frequency reference (speed

agree).

Default: 0.0 Hz

Min.: 0.0

Max.: 400.0

189

B.5 d: References

426

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual