beautypg.com

C: tuning, C1: acceleration and deceleration times, 3 c: tuning – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 176: C1-11: accel/decel time switching frequency

background image

5.3 C: Tuning

C parameters set the characteristics for acceleration, deceleration, and S-curves. Other parameters in the C group cover settings

for slip compensation, torque compensation, and carrier frequency.

u

C1: Acceleration and Deceleration Times

n

C1-01 to C1-04: Accel, Decel Times 1 and 2

Two different sets of acceleration and deceleration times can be set in the drive by digital inputs, motor selection, or switched

automatically.
Acceleration time parameters always set the time to accelerate from 0 Hz to the maximum output frequency (E1-04).

Deceleration time parameters always set the time to decelerate from maximum output frequency to 0 Hz. C1-01 and C1-02

are the default active accel/decel settings.

No.

Parameter Name

Setting Range

Default

C1-01

Acceleration Time 1

0.0 to 6000.0 s

<1>

10.0 s

C1-02

Deceleration Time 1

C1-03

Acceleration Time 2

C1-04

Deceleration Time 2

<1> The setting range for the acceleration and deceleration times is determined by the accel/decel time setting units in C1-10. For example, if the time

is set in units of 0.01 s (C1-10 = 0), the setting range becomes 0.00 to 600.00 s.

Switching Acceleration Times by Digital Input

Accel/decel time 1 is active by default if no input is set. Activate accel/decel times 2, 3, and 4 by digital inputs

(H1-oo = 7 and 1A) as explained in

Table 5.13

.

Table 5.13 Accel/Decel Time Selection by Digital Input

Accel/Decel Time Sel. 1

H1-oo = 7

Accel/Decel Time Sel. 2

H1-oo = 1A

Active Times

Acceleration

Deceleration

0

0

C1-01

C1-02

1

0

C1-03

C1-04

Figure 5.22

shows an operation example for changing accel/decel. times. The example below requires that the stopping method

be set for “Ramp to stop” (b1-03 = 0).

Output

frequency

Accel Time 1

(C1-01)

Decel Time 1

(C1-02)

Accel Time 2

(C1-03)

Decel Time 2

(C1-04)

Decel Time 1

(C1-02)

Time

FWD (REV)

Run command

ON

OFF

ON

ON

Accel/Decel Time Selection 1

(Terminals S1 to S8, H1-oo = “7”)

OFF

Figure 5.22 Timing Diagram of Accel/Decel Time Change

n

C1-11: Accel/Decel Time Switching Frequency

Sets the frequency at which the drive switches between accel/decel time settings.

No.

Parameter Name

Setting Range

Default

C1-11

Accel/Decel Time Switching Frequency

0.0 to 400.0 Hz

0.0 Hz

5.3 C: Tuning

176

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual