beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 232

background image

n

H6-08: Pulse Train Input Minimum Frequency

Sets the minimum output frequency detected by the pulse train input. Increasing this setting reduces the time the drive needs

to react to changes in the input signal.
• The pulse input value becomes 0 when the pulse input frequency falls below this level.
• Enabled when H6-01 = 0, 1, or 2.
• When simple speed feedback in V/f Control is set as the function for terminal RP (H6-01 = 3), the minimum frequency

becomes the detection time for PG disconnect (F1-14).

No.

Name

Setting Range

Default

H6-08

Pulse Train Input Minimum Frequency

0.1 to 1000.0 Hz

0.5 Hz