B.15 defaults by drive model – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 482

No.
Name
Unit
Default Settings
–
Model CIMR-Po
–
5A0125
5A0145
5A0192
5A0242
o2-04
Drive Model Selection
Hex.
D5
D6
D7
D9
E2-11
Motor Rated Power
kW (HP)
90
(125)
110
(150)
160
(200)
185
(250)
b3-04
V/f Gain during Speed Search
%
80
80
80
80
b3-06
Output Current 1 during Speed Search
–
0.5
0.5
0.5
0.5
b3-07
Output Current 2 during Speed Search
(Speed Estimation Type)
–
–
–
–
–
b3-26
Start Speed Search Select
–
–
–
–
–
b8-03
Energy Saving Control Filter Time Constant
s
2.00
2.00
2.00
2.00
b8-04
Energy Saving Coefficient Value
–
61.50
58.67
49.90
42.90
C5-17
Motor Inertia
kgm
2
1.10
1.90
2.10
4.10
C6-02
Carrier Frequency Selection
–
7
7
7
7
E2-01
Motor Rated Current
A
125
145
192
242
E2-02
Motor Rated Slip
Hz
1.39
1.40
1.35
1.35
E2-03
Motor No-Load Current
A
37.5
43.2
57.6
57.6
E2-05
Motor Line-to-Line Resistance
Ω
0.079
0.060
0.037
0.037
E2-06
Motor Leakage Inductance
%
20.0
20.0
20.0
20.0
E2-10
Motor Iron Loss for Torque Compensation
W
2150
2150
2850
2850
L2-02
Momentary Power Loss Ride-Thru Time
s
2.0
2.0
2.0
2.0
L2-03
Momentary Power Loss Minimum Baseblock Time
s
2.0
2.0
2.0
2.0
L2-04
Momentary Power Loss Voltage Recovery Time
s
1.7
1.8
2.0
2.0
L3-24
Motor Acceleration Time for Inertia Calculations
s
0.592
0.646
0.673
0.864
L8-02
Overheat Alarm Level
°C
110
110
110
110
L8-35
Installation Method Selection
–
0
0
0
0
L8-38
Carrier Frequency Reduction Selection
–
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
30
30
30
30
B.15 Defaults by Drive Model
482
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual