beautypg.com

Canopen parameters, Devicenet parameters – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 201

background image

No.

Parameter Name

Setting Range

Default

F6-30

PROFIBUS-DP Node Address

0 to 125

0

n

F6-31: PROFIBUS-DP Clear Mode Selection

Determines the operation when a Clear Mode command is received.

No.

Parameter Name

Setting Range

Default

F6-31

PROFIBUS-DP Clear Mode Selection

0, 1

0

Setting 0: Reset

Resets the drive operation (frequency reference, inputs, outputs etc.).

Setting 1: Maintain the Previous State

Returns the drive status to the state prior to receiving the command.

n

F6-32: PROFIBUS-DP Data Format Selection

Selects the data format used for PROFIBUS-DP communication.

No.

Parameter Name

Setting Range

Default

F6-32

PROFIBUS-DP Data Format Selection

0, 1

0

Setting 0: PPO-type Data Format

Setting 1: Conventional Data Format

u

CANopen Parameters

Parameters F6-35 and F6-36 set the drive to operate on a CANopen network.

n

F6-35: CANopen Node ID Selection

Selects the node ID of a CANopen option board.

No.

Parameter Name

Setting Range

Default

F6-35

CANopen Node ID Selection

0 to 126

0

n

F6-36: CANopen Communication Speed

Sets the communication speed for a CANopen option card.

No.

Parameter Name

Setting Range

Default

F6-36

CANopen Communication Speed

0 to 8

6

Setting 0: Auto detection
Setting 1: 10 kbps
Setting 2: 20 kbps
Setting 3: 50 kbps
Setting 4: 125 kbps
Setting 5: 250 kbps
Setting 6: 500 kbps
Setting 7: 800 kbps
Setting 8: 1 Mbps

u

DeviceNet Parameters

Parameters F6-50 through F6-63 set the drive to operate on a DeviceNet network.

n

F6-50: DeviceNet MAC Address

Sets the MAC address for a DeviceNet option card.

5.6 F: Option Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

201

5

Parameter Details

This manual is related to the following products: