Use parameters o1-07 and o1-08 to select and fix the second and third monitors shown in the Home (Frequency Reference)

and Monitor screen to ensure that those monitors are always visible when scrolling through the monitor list.

No.

Name

Setting Range

Default

o1-06

User Monitor Selection Mode

0, 1

0

Setting 0: 3 Mon Sequential (displays the next 2 sequential monitors)
Setting 1: 3 Mon Selectable (set by o1-07 and o1-08)

n

o1-07: Second Line User Monitor Selection

Selects the monitor that is shown in the second line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set “403” to display

monitor parameter U4-03.

No.

Name

Setting Range

Default

o1-07

Second Line User Monitor Selection

101 to 799

102

n

o1-08: Third Line User Monitor Selection

Selects the monitor that is shown in the third line. Effective only when o1-06 is set to 1.
Enter the last three digits of the monitor parameter number to be displayed: Uo-oo. For example, set “403” to display

monitor parameter U4-03.

No.

Name

Setting Range

Default

o1-08

Second Line User Monitor Selection

101 to 799

103

n

o1-09: Frequency Reference Display Units

Selects the monitor that is shown in the third line. Enter the last three digits of the monitor parameter number to be displayed:

Uo-oo. For example, set "403" to display monitor parameter U4-03.

Note:

Parameter is effective only when o1-06 is set to 1.

No.

Name

Setting Range

Default

o1-09

Frequency Reference Display Units

0 to 15; 24, 25

25

Setting 0: Inch of Water (WC)
Setting 1: Pounds per Square Inch (PSI)
Setting 2: Gallons per Minute (GPM)
Setting 3: Degrees Fahrenheit (F)
Setting 4: Cubic Feet per Minute (CFM)
Setting 5: Cubic Meters per Hour (CMH)
Setting 6: Liters per Hour (LPH)
Setting 7: Liters per Second (LPS)
Setting 8: Bar (Bar)
Setting 9: Pascals (Pa)
Setting 10: Degrees Celsius (C)
Setting 11: Meters (Mtr)
Setting 12: Feet (Ft)
Setting 13: Liters per Minute (LPN)
Setting 14: Cubic Meters per Minute (CMM)
Setting 15: Inches of Mercury (Hg)
Setting 24: Custom Units (determined by o1-13 to o1-15)
Setting 25: None

n

o1-10: User-Set Display Units Maximum Value

Determines the display value that is equal to the maximum output frequency.

5.10 o: Operator Related Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

267

5

Parameter Details