(Addr.

Hex)

Name

Description

Values

Page

L8-19

(4BF)

Frequency Reduction Rate

during Overheat Pre-Alarm

Specifies the frequency reference reduction gain at overheat pre-alarm when

L8-03 = 4.

Default: 0.8

Min.: 0.1

Max.: 0.9

258

L8-32

(4E2)

Main Contactor and Cooling

Fan Power Supply Failure

Selection

Determines drive response when a fault occurs with the internal cooling fan.

0: Ramp to stop

1: Coast to stop

2: Fast stop (Decelerate to stop using the deceleration time set to C1-09)

3: Alarm only (“FAn” will flash)

4: Continue operation at reduced speed as set to L8-19.

Default: 1

Range: 0 to 4

260

L8-35

(4EC)

Installation Method

Selection

0: IP00/Open-Chassis enclosure

1: Side-by-Side mounting

2: IP20/NEMA Type 1 enclosure

3: Finless model drive or external heatsink installation

Default:

<2> <3>

Range: 0 to 3

260

L8-38

(4EF)

Carrier Frequency

Reduction

0: Disabled

1: Enabled below 6 Hz

2: Enabled for the entire speed range

Default: 2

Range: 0 to 2

261

L8-40

(4F1)

Carrier Frequency

Reduction Off Delay Time

Sets the time that the drive continues running with reduced carrier frequency

after the carrier reduction condition is gone. Setting 0.00 s disables the carrier

frequency reduction time.

Default: 0.5 s

Min.: 0.00

Max.: 2.00

261

L8-41

(4F2)

High Current Alarm

Selection

0: Disabled

1: Enabled. An alarm is triggered at output currents above 150% of drive rated

current.

Default: 0

Range: 0, 1

261

L8-55

(45F)

Internal Braking Transistor

Protection

0: Disabled. Disable when using a regen converter or optional braking unit.

1: Protection enabled.

Default: 1

Range: 0, 1

261

L8-93

(73C)

LSo Detection Time at Low

Speed

Sets the amount of time until baseblock is executed after detecting pull-out at

low speed.

Default: 1.0 s

Min.: 0.0

Max.: 10.0

262

L8-94

(73D)

LSo Detection Level at Low

Speed

Determines the detection level of pull-out at low speed.

Default: 3%

Min.: 0

Max.: 10

262

L8-95

(73D)

Average LSo Frequency at

Low Speed

Sets the average number of times pull-out can occur at low speed.

Default: 10 times

Min.: 1

Max.: 50

262

<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Parameter setting value is not reset to the default value when the drive is initialized.
<3> Default setting is determined by the drive model:

Setting 2: Model code CIMR-Po2A0004 to 2A0211, 4A0002 to 4A0165, and 5A0003 to 5A0242
Setting 0: Model code CIMR-Po2A0250 to 2A0415 and 4A0208 to 4A0675

B.8 L: Protection Function

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

447

B

Parameter List