beautypg.com

Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 157

background image

n

b3-04: V/f Gain During Speed Search

During Speed Search, the output voltage calculated from the V/f pattern is multiplied with this value. Changing this value can

help reduce the output current during Speed Search.

No.

Name

Setting Range

Default

b3-04

V/f Gain During Speed Search

10 to 100%

Determined by

o2-04

n

b3-05: Speed Search Delay Time

In cases where an output contactor is used between the drive and the motor, the contactor must be closed before Speed Search

can be performed. This parameter can be used to delay the Speed Search operation, giving the contactor enough time to close

completely.

No.

Name

Setting Range

Default

b3-05

Speed Search Delay Time

0.0 to 100.0 s

0.2 s

n

b3-06: Output Current 1 During Speed Search

Sets the current injected to the motor at the beginning of Speed Estimation Speed Search as a coefficient for the motor rated

current.

No.

Name

Setting Range

Default

b3-06

Output Current 1 during Speed Search

0.0 to 2.0

Determined by

o2-04

n

b3-07: Output Current 2 during Speed Search (Speed Estimation Type)

Sets the amount of output current during Speed Estimation Speed Search as a coefficient for the no-load current. Output current

during Speed Search is automatically limited by the drive rated current. Increase this setting value in increments of 0.1 if the

drive fails to perform Speed Estimation

Note:

This parameter is only available in models 4A0930 and 4A1200.

No.

Name

Setting Range

Default

b3-07

Output Current 2 during Speed Search (Speed Estimation Type)

0.0 to 5.0

Determined by

o2-04

n

b3-08: Current Control Gain during Speed Search (Speed Estimation Type)

Sets the proportional gain for the current controller during Speed Search.

No.

Name

Setting Range

Default

b3-08

Current Control Gain during Speed Search (Speed Estimation Type)

0.00 to 6.00

0.8

n

b3-10: Speed Search Detection Compensation Gain

Sets the gain for the detected motor speed of the Speed Estimation Speed Search. Increase the setting only if an overvoltage

fault occurs when the drive restarts the motor.

No.

Name

Setting Range

Default

b3-10

Speed Search Detection Compensation Gain

1.00 to 1.20

1.05

n

b3-12: Minimum Current Detection Level during Speed Search

Sets the minimum current detection level during Speed Search. Increase this setting value in increments of 0.1 if the drive

fails to perform Speed Estimation.

Note:

This parameter is only available in models 4A0930 and 4A1200.

No.

Name

Setting Range

Default

b3-12

Minimum Current Detection Level during Speed Search

2.0 to 10.0

6.0

n

b3-14: Bi-Directional Speed Search Selection

Sets how the drive determines the motor rotation direction when performing Speed Estimation Speed Search.

5.2 b: Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

157

5

Parameter Details

This manual is related to the following products: