Installing the cooling fan unit – Yaskawa AC Drive-P1000 Industrial Fan User Manual

Page 368

background image

Circulation Fan B10

Circulation Fan B9

Fun Unit Case (R)

Circulation Fan B8

Circulation Fan B7

Hook

Relay Connector

Hook

Fun Unit Case (L)

Relay Connector

Figure 7.48 Cooling Fan Wiring: 4A0930 and 4A1200

9.

Replace the circuit board cooling fans.

Note:

Figure 7.49

shows the right side circuit board cooling fan.

A

B

A – Circuit board cooling fan

B – Circuit board cooling fan case

Figure 7.49 Fan Unit Disassembly: 4A0930 and 4A1200

10.

Position the protective tube so the fan connector sits in the center of the protective tube. (Circuit board cooling fans

only)

Protective tube

11.

Guide the lead wires through the provided hooks so the wires are held in place.

Circuit Board Cooling Fan B6

Circuit Board Cooling Fan B7

Relay Connector

Relay Connector

Figure 7.50 Cooling Fan Wiring: 4A0930 and 4A1200

12.

Double-check the relay connector to ensure that it is properly connected.

n

Installing the Cooling Fan Unit

1.

Reverse the procedure described above to reinstall the cooling fan unit.

Note:

Properly connect the relay connectors to the fan unit connectors.

7.4 Drive Cooling Fans

368

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual