The PID acceleration/deceleration time can be canceled using a digital input programmed for “PID SFS cancel” (H1-oo =

34).

No.

Name

Setting Range

Default

b5-17

PID Accel/Decel Time

0.0 to 6000.0 s

0.0 s

n

b5-18: PID Setpoint Selection

Enables or disables parameter b5-19 for PID setpoint.
Refer to

Figure 5.18

for the digital operator home screen display when PID is enabled and b5-18 is set to 1, enabling PID

Setpoint Selection.

U5-99= 30.00%

U5-01= 50.55%

U5-02= -50.55%

PID Setpoint Cmd

- MODE -

DRV RDY

LSEQ

RREF

JOG

b5-19= 030.00%

(0.00~100.00)

“0.00%”

PID Setpoint

- MONITR -

DRV RDY

ENTER

ESC

ENTER

Figure 5.18 PID Setpoint Selection Display

No.

Parameter Name

Setting Range

Default

b5-18

PID Setpoint Selection

0, 1

0

Setting 0: Disabled

Parameter b5-19 is not used as the PID setpoint.

Setting 1: Enabled

Parameter b5-19 is used as PID setpoint.

n

b5-19: PID Setpoint Value

Used as the PID setpoint if parameter b5-18 = 1.

Note:

Values set above b5-38 will be internally limited to b5-38.

No.

Name

Setting Range

Default

b5-19

PID Setpoint Value

0.00 to 600.00%

0.00%

u

EZ Sleep/Wake-up Function

To enable EZ Sleep/Wake-up functionality on the drive, first set parameter b5-89 to 1. The default setting for b5-89 is 0, which

disables the EZ Sleep functionality and related parameters, except for parameter b5-91, EZ Sleep Minimum Speed.
Setting b5-89 to 1 disables the existing PID Sleep function (b5-15) and enables the EZ Sleep/Wake-up functionality.
EZ Sleep and Minimum Speed Units
Parameter b5-90, EZ Sleep Unit, determines the unit, range, and resolution of parameters b5-92 and b5-93. When set to Hz,

the range is 0.1 to 400.0 Hz. When set to RPM, the range is 0 to 24000 RPM. Changing b5-90 will NOT automatically re-

scale the values of b5-92 and b5-93.
Minimum Speed
Parameter b5-91, EZ Minimum Speed, acts as a lower limit on the PID output. This value is internally limited to the higher

value between b5-34 or d2-02 and is active regardless of the b5-89 setting. When this limit is active, the PID integrator will

be held to avoid integral wind-up. Parameter b5-90 determines whether the value is input in Hz or RPM.
Sleep
When the output frequency (or speed) is at or below the EZ Sleep Level (b5-92) for the time set in EZ Sleep Time (b5-93),

the drive will sleep. The EZ Sleep Level is internally lower limited to the b5-92 setting.
Wake-up using Absolute Level (b5-95 = 0)
For Normal Acting PID, the PID Feedback must drop below the EZ Wake-up Level (b5-94) for the time set in EZ Wake-up

Time (b5-96) in order for the drive to wake-up.

5.2 b: Application

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

167