Memobus/modbus setup parameters, Memobus/modbus serial communication, C.4 memobus/modbus setup parameters – Yaskawa AC Drive-P1000 Industrial Fan User Manual
Page 489: Refer to memobus/modbus serial, For detailed descriptions of the h5
C.4 MEMOBUS/Modbus Setup Parameters
u
MEMOBUS/Modbus Serial Communication
Changes to MEMOBUS/Modbus communications settings become effective after restarting the drive.
n
H5-01: Drive Node Address
Sets the drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S- . .
Note:
Cycle the power after changing this parameter to enable the new setting.
No.
Name
Setting Range
Default
H5-01
Drive Slave Address
1F (Hex)
n
H5-02: Communication Speed Selection
Sets the MEMOBUS/Modbus communications speed.
Note:
Cycle the power after changing this parameter to enable the new setting.
No.
Name
Setting Range
Default
H5-02
Communication Speed Selection
0 to 8
3
H5-02
Communication Speed
H5-02
Communication Speed
0
1200 bps
5
38400 bps
1
2400 bps
6
57600 bps
2
4800 bps
7
76800 bps
3
9600 bps
8
115200 bps
4
19200 bps
n
H5-03: Communication Parity Selection
Sets the parity used for communications.
Note:
Cycle the power after changing this parameter to enable the new setting.
No.
Name
Setting Range
Default
H5-03
Communication Parity Selection
0 to 2
0
Setting 0: No parity
Setting 1: Even parity
Setting 2: Odd parity
n
H5-04: Stopping Method after Communication Error
Selects the stopping method after a communications error (CE) has occurred.
No.
Name
Setting Range
Default
H5-04
Stopping Method after CE
0 to 3
3
Setting 0: Ramp to stop (uses the deceleration time currently enabled)
Setting 1: Cost to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
n
H5-05: Communication Fault Detection Selection
Enables or disables the CE detection for communications.
No.
Name
Setting Range
Default
H5-05
Communication Fault Detection Selection
0 or 1
1
Setting 0: Disabled
No communication error detection. The drive continues operation.
C.4 MEMOBUS/Modbus Setup Parameters
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
489
C
MEMOBUS/Modbus Communications