Setting 1: Coast to Stop

Setting 2: Fast Stop

Setting 3: Alarm Only (Continue Operation)

n

F6-07: NetRef/ComRef Function Selection

Selects the treatment of multi-step speed inputs when the NetRef command is set.

No.

Parameter Name

Setting Range

Default

F6-07

NetRef/ComRef Function Selection

0, 1

0

Setting 0: Multi-step Speed Operation Disabled

Multi-step speed input frequency references are disabled when the NetRef command is selected.

Setting 1: Multi-step Speed Operation Enabled

Multi-step speed inputs are still active and can override the frequency reference from the communications option even when

the NetRef command is selected.

n

F6-08: Reset Communication Parameters

Determines whether F6-oo/F7-oo communication-related parameters are reset after initialization.

No.

Parameter Name

Setting Range

Default

F6-08

Reset Communication Parameters

0, 1

0

Setting 0: Do Not Reset F6-oo/F7-oo Parameters after Initialization Using A1-03

Setting 1: Reset F6-oo/F7-oo Parameters after Initialization Using A1-03

Note:

F6-08 is not reset when the drive is initialized.

u

CC-Link Parameters

Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.

n

F6-04: bUS Error Detection Time

Sets the delay time for bUS error detection.

No.

Parameter Name

Setting Range

Default

F6-04

bUS Error Detection Time

0.0 to 5.0 s

2.0 s

n

F6-10: CC-Link Node Address

Sets the node address of a CC-Link option board.

No.

Parameter Name

Setting Range

Default

F6-10

CC-Link Node Address

0 to 64

0

n

F6-11: CC-Link Communication Speed

Sets the communication speed for a CC-Link option card.

No.

Parameter Name

Setting Range

Default

F6-11

CC-Link Communication Speed

0 to 4

0

Setting 0: 156 kbps
Setting 1: 625 kbps
Setting 2: 2.5 Mbps
Setting 3: 5 Mbps
Setting 4: 10 Mbps

n

F6-14: CC-Link bUS Error Auto Reset

Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.

5.6 F: Option Settings

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual

199

5

Parameter Details