Setting 1: Coast to Stop
Setting 2: Fast Stop
Setting 3: Alarm Only (Continue Operation)
n
F6-07: NetRef/ComRef Function Selection
Selects the treatment of multi-step speed inputs when the NetRef command is set.
No.
Parameter Name
Setting Range
Default
F6-07
NetRef/ComRef Function Selection
0, 1
0
Setting 0: Multi-step Speed Operation Disabled
Multi-step speed input frequency references are disabled when the NetRef command is selected.
Setting 1: Multi-step Speed Operation Enabled
Multi-step speed inputs are still active and can override the frequency reference from the communications option even when
the NetRef command is selected.
n
F6-08: Reset Communication Parameters
Determines whether F6-oo/F7-oo communication-related parameters are reset after initialization.
No.
Parameter Name
Setting Range
Default
F6-08
Reset Communication Parameters
0, 1
0
Setting 0: Do Not Reset F6-oo/F7-oo Parameters after Initialization Using A1-03
Setting 1: Reset F6-oo/F7-oo Parameters after Initialization Using A1-03
Note:
F6-08 is not reset when the drive is initialized.
u
CC-Link Parameters
Parameters F6-04, F6-10, F6-11, and F6-14 set the drive to operate on a CC-Link network.
n
F6-04: bUS Error Detection Time
Sets the delay time for bUS error detection.
No.
Parameter Name
Setting Range
Default
F6-04
bUS Error Detection Time
0.0 to 5.0 s
2.0 s
n
F6-10: CC-Link Node Address
Sets the node address of a CC-Link option board.
No.
Parameter Name
Setting Range
Default
F6-10
CC-Link Node Address
0 to 64
0
n
F6-11: CC-Link Communication Speed
Sets the communication speed for a CC-Link option card.
No.
Parameter Name
Setting Range
Default
F6-11
CC-Link Communication Speed
0 to 4
0
Setting 0: 156 kbps
Setting 1: 625 kbps
Setting 2: 2.5 Mbps
Setting 3: 5 Mbps
Setting 4: 10 Mbps
n
F6-14: CC-Link bUS Error Auto Reset
Selects whether a bUS error can be automatically reset if automatic fault retry is enabled.
5.6 F: Option Settings
YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual
199