Digital Operator Display

Fault Name

FbL

PID Feedback Loss
PID feedback loss detection is programmed to trigger a fault (b5-12 = 2 or 5) and the PID feedback level

is below the detection level set to b5-13 for longer than the time set to b5-14.

Cause

Possible Solution

Parameters are set inappropriately

Check b5-13 and b5-14 settings.

Incorrect PID feedback wiring

Correct the wiring.

There is a problem with the feedback sensor

• Check the sensor on the control side.
• Replace the sensor if damaged.

Digital Operator Display

Fault Name

GF

Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.

Cause

Possible Solution

Motor insulation is damaged

• Check the insulation resistance of the motor.
• Replace the motor.

A damaged motor cable is creating a short

circuit

• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.

Excessive leakage current at the drive output

• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.

The drive started to run during a current offset

fault or while coasting to a stop

• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-oo = 61 or 62) via one of the external terminals.

Hardware problem

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

Digital Operator Display

Fault Name

LF

Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.

Cause

Possible Solution

The output cable is disconnected

• Check for wiring errors and properly connect the output cable.
• Correct the wiring.

The motor winding is damaged

• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.

The output terminal is loose

• Apply the tightening torque specified in this manual to fasten the terminals.

Refer to Main Circuit

Wire Gauges and Tightening Torque on page 85

for details.

The rated current of the motor being used is

less than 5% of the drive rated current

Check the drive and motor capacities.

An output transistor is damaged

If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the control board.

A single-phase motor is being used

The drive cannot operate a single phase motor.

Digital Operator Display

Fault Name

<1>

LF3

Power Unit Output Phase Loss 3
• Phase loss occurred on the output side
• Setting L8-78 to 1 enables Power Unit Output Phase Loss Protection

Cause

Possible Solution

The gate drive board in the power unit is

damaged.

Cycle the power supply.

Refer to Diagnosing and Resetting Faults on page 326

for details. If the fault

continues to occur, replace the gate drive board or the entire drive. Contact Yaskawa or a Yaskawa

representative for instructions on replacing the gate drive board.

Cable to the current detection circuit in the

power unit is damaged or not connected

properly.

Check for incorrect wiring and correct any wiring mistakes.

6.4 Fault Detection

300

YASKAWA SIEP YAIP1U 01B AC Drive - P1000 Technical Manual